Belimo UK24LON Product Information - Page 12
Browse online or download pdf Product Information for Gateway Belimo UK24LON. Belimo UK24LON 16 pages. Gateway mp/lonworks

Operation, Characteristics
Legend for operating controls
Power LED
1
Error LED
2
Test in progress LED
3
MP address display
4
Registered actuator LED
5
Individual Neuron ID
6
Status LED function according to
7
Echelon Guidelines
Service button for commissioning
8
with L
W
ORKS ®
ON
Unit power supply AC or DC 24 V
9
SET button for MP addressing
10
Up button for MP addresses
11
Start test button
12
MP connector: For connecting
13
MFT(2)/MP actuators
MFT-H connector: For connecting the
14
MFT parameterising tool
ORKS ®
L
W
connector
15
ON
Node label
16
The operating controls numbered
2
3
4
5
7
10 11 12
are described below in greater detail.
Operation, characteristics of the UK24LON unit
Automatic scanning
of the MP network
As soon as the UK24LON unit is power-
ed up it starts scanning the MP network
automatically. All eight MP addresses are
interrogated cyclically to see whether the-
re is an actuator available to respond. The
results are compared against a reference
table stored in the UK24LON unit. If an ac-
tuator responds from an MP address that
is not assigned in the reference table it is
automatically inserted into the table.
If an actuator already assigned in the refer-
ence table fails to respond an error alarm
is initiated but the reference table is not
altered in any way. The actuators can be
pre-addressed so that they are recognis-
ed automatically when they are connect-
ed to the MP network.
Manual addressing
of actuators
All required actuators must be connect-
●
ed first.
Use the Up button
11
●
address to be issued. The actual add-
ress will be shown on the display
Use the Set button
10
●
addressing process (hold for at least
2 seconds). The Reg'd LED
flashing slowly (at
1
⁄
second intervals)
2
to indicate that the process is in pro-
gress.
12
1
16
Within the next 10 minutes, the MFT(2)/
●
MP actuator being addressed must be
reset (in the case of standard damper
actuators by pressing the addressing
button; in the case of spring return ac-
tuators by moving the L/R switch back
and forth and in the case of globe valve
actuators by pressing the S2 button).
The UK24LON unit will then be able to
recognise and address the actuator.
This status is indicated by fast flashing
of the Reg'd LED
As soon as addressing of the actua-
●
tor has been completed the Reg'd LED
– gives a steady light. This also indi-
5
cates that the MP address has been
successfully stored in the reference ta-
ble of the UK24LON unit.
Notes on addressing
If none of the actuators has been re-
●
set within 10 minutes of the addressing
process being initiated, the process will
be discontinued. The reference table re-
to select the
mains unchanged and the Reg'd LED
-
stops flashing.
5
.
4
If an address is issued that has already
●
to start the
been assigned to another actuator the
latter is automatically de-addressed first
starts
5
before the new actuator is addressed.
If a mistake is made in initiating address-
●
ing, the process can be stopped by
briefly pressing the Set button
2
3
NID: XXXXXXXXXXXX
UK24LON
UK24-LON
Made in Switzerland
Test in
Power
Error
Progress
Node
MFT - H
Test
IC-DZ.03
LonTalk
MP-Com.
a
b
0V
24V
Y
U/MP
15 14
13
.
5
.
10
4
5
Address
Reg'd
Status
Select
Service
Up
Set
Power
0V
24V
n.c.
12 11 10
9
Normal data traffic on the MP network
●
is interrupted while addressing is in pro-
gress.
Manual de-addressing
of MFT(2)/MP actuators
All actuators that are to be de-addressed
●
must be connected first.
Press the Up button
11
●
address to be deleted. The current
address is shown on the display
Start de-addressing by pressing the
●
Set button
(min. 2 s). The Reg'd LED
10
flashes slowly as a check (every
5
second).
Press the Set button
a second time
●
10
until the Reg'd LED
flashes rapidly.
5
The Reg'd LED
goes out after the
5
●
actuator has been de-addressed, i.e.
removed from the reference table and
set to the address "PP".
6
7
8
to select the
.
4
1
⁄
2