UK24MOD
Version overview
Firmware V1.08
Firmware V1.07
Firmware V1.06
Firmware V1.05
Firmware V1.04
Firmware V1.03
www.belimo.com
Belimo Gateway MP to Modbus RTU
New functions/modifications:
Bug fix: Modbus telegrams longer than 20 Bytes (e.g. ReadHoldingRegister with more
than 8 registers) are properly handled
Bug fix: Detection of new MP actuator in operation
New functions:
New register for reading of nominal volumetric flow
Support for MPL actuators
Note on compatibility:
Service information can be found in registers 1001 to 1004 (former 161 to 164)
Known issues:
Modbus telegrams longer than 20 Bytes (e.g. ReadHoldingRegister with more than 8
registers) cause wrong register entries.
New functions:
Timeout period for fire & smoke increased from 60 to 120 seconds (Register 2).
Higher numbers of nodes realizable per Modbus master.
New functions:
New registers for adjusting Min (14) and Max (15) setting.
New register for reading of absolute volumetric flow.
New functions:
Parity/Character transmission adjustable via DIP switch:
NONE (1, 8, N, 2) or EVEN (1, 8, E, 1)
Release without restrictions
T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes