DuraVent DCL 8 WS E Instructions Manual - Page 3

Browse online or download pdf Instructions Manual for Ventilation Hood DuraVent DCL 8 WS E. DuraVent DCL 8 WS E 16 pages. Positive pressure systems

SECTION B - GENERAL INFORMATION

PART NUMBERS
These instructions identify major model parts by name and part number.
Example:
DIS1 - 36" length with inside diameter 14" made of 316SS flue (inner w a l l ) and
304SS (outer casing).
DIS1
14
L36
BC
Model
Dia.
Part Material Type
DAS1 - 30° elbow with inside diameter 22" made of 30SS flue (inner wall)
and galvalume (outer casing).
DAS1
22
E30
CE
Model
Dia.
Part Material Type
DCL - single wall support for 8" diameter grease duct made of galvalume.
DCL
8
WS
E
Model
Dia
Part
Material Type
Use only factory-supplied components. Failure to do so will void the
certification and the warranty of the grease duct system.
EFFECTIVE LENGTH
The effective length is the length of the part when it is assembled.
Effective length
L36 ................36 1/16"
L24 ................24 1/16"
L18 ................17 9/16"
L12 ................11 9/16"
CLEARANCE
DuraVent Models D CL, DAS - PRO a n d DI S- PRO are primarily intended to be
used in a non-combustible surrounding. Only Models DAS-PRO and DIS-PRO can
be used for either combustible or non-combustible surroundings. When installed
in an open room where enclosure is not required, the chimney may be located
at a minimum clearance to adjacent combustible walls in accordance with Table
1. The chimney may be located in corners formed by two combustible
constructions (walls, floor, ceiling, supports, etc.)
NOTE: The clearance distance with the wall is the distance between the wall and
the inner V-Band for model DCL or the Outer Band (BSE) for model DAS-PRO and
DIS-PRO. See Table 1 for the clearance distance.
For non-combustible construction, maintain clearance as required for installation
access for inspection or per local code. In buildings more than one story in height
and in one-story buildings where the roof-ceiling assembly is required to have a fire
resistance rating, the duct must be enclosed in a continuous enclosure from the
lowest fire-rated ceiling or floor above the hood, through any concealed spaces,
to or through the roof to maintain the integrity of the fire separations required
by the applicable building code provisions. If the building is less than 4 stories
in height, the enclosure shall have a fire resistance rating of not less than 1
hour. If the building is 4 stories or more in height, the enclosure shall have a fire
resistance rating not less than 2 hours.
DuraVent models DAS-PRO and D I S -PRO chimneys may penetrate a combustible
floor, wall, or roof using the appropriate parts and openings sizes. See Section D
"Roof and Wall Penetration" for more details.
NOTE: Do not enclose with combustible materials
In the case of a fire rated enclosure made of non-combustible or limited
combustible construction, the minimum clearance with the Model
be 6" or as required by local code.
 
OPENING THROUGH CONSTRUCTION 
The following table serves to identify the minimum opening required
when installing a chimney through a floor, wall or roof made of
combustible material. See
D
CL must
 
S
R
D
S
UBMITTAL 
ECORD FOR 
URA
TACK 
M&G
D
V
|
10
J
 
URA
ENT 
 
 
UPITER 
www.duravent.com 
TABLE 1 –
Minimum Air Space CLEARANCE to
Unenclosed Combustible Surroundings
(adjacent to maximum of two [2] walls)
Flue Diameter Ø
Vent Model
(in)
DCL
5 to 36
5 and 6
7 to 14
DAS1
16 to 22
24 to 30
32 to 36
5 and 6
7 to 14
DIS1
16 to 22
(UL103 Type HT
5" to 24" only)
24 to 30
32 to 36
5 to 14
DIS2 &
DIS4
16 to 30
(UL103 Type HT
5" to 24" only)
32 to 36
Dimensions are in inches
Table 2.
TABLE 2 -
Openings in Floor / Wall / Roof – for ALL
MODELS
Flue
Combustible
Vent
Diameter
Roof, Floor
Model
Ø
or Wall
(in)
(in)
DCL
5 to 36
ID + 37 – ¼"
5 and 6
ID + 10 – ¾"
7 to 9
ID + 12 – ¾"
10 to 14
DAS1
16 to 22
ID + 14 – ¾"
24 to 30
ID + 16 – ¾"
32 to 36
ID + 18 – ¾"
5 and 6
ID + 4 – ¾"
7 to 9
ID + 6 – ¾"
10 to 14
DIS1
16 to 22
ID + 8 – ¾"
24 to 30
ID + 10 – ¾"
32 to 36
ID + 12 – ¾"
5 to 7
ID + 6 – ¾"
8 to 14
DIS2
16 to 30
ID + 8 – ¾"
32 to 36
ID + 10 – ¾"
5 to 7
ID + 10 – ¾"
8 to 14
DIS4
16 to 30
ID + 12 – ¾"
32 to 36
ID + 14 – ¾"
Dimensions are in inches
M
DCL,
DAS1,
DIS1,
DIS2
ODELS 
 
 
 
 AND 
L
|
A
,
N
Y
 
ANE 
 
LBANY
 
EW 
ORK
Clearance to
Clearance to
Non-
Combustible
Combustible
(in)
(in)
18
0
4
0
5
0
6
0
7
0
8
0
1
0
2
0
3
0
4
0
5
0
1
0
2
0
3
0
Non-Combustible
Roof / Floor / Wall
(in)
Uninstalled
Installed Stacks
Stacks ( NO
(locking Bands
locking Bands
Installed)
Installed)
ID + 2 – ½"
ID + 1 – 1/8"
ID + 4 – ½"
ID + 2 – ¾"
ID + 3 – ½"
ID + 4 – ½"
ID + 2 – ¾"
ID + 3 – ½"
ID + 6 – ½"
ID + 4 – ¾"
ID + 5 – ½"
ID + 10 – ½"
ID + 8 – ¾"
ID + 9 – ½"
DIS4