DuraVent DuraChimney II Installation Instructions Manual - Page 5
Browse online or download pdf Installation Instructions Manual for Ventilation Hood DuraVent DuraChimney II. DuraVent DuraChimney II 16 pages. Air-cooled, all-fuel chimney for fireplaces
CHIMNEY DIAMETER
Follow the fireplace manufacturer's manual
to determine required chimney diameter and
clearances between combustible materials
and your fireplace. Never use a chimney
with an inside diameter smaller than your
flue opening above firebox unless specifically
allowed by the fireplace manufacturer. If you
are connecting to a masonry fireplace, refer to
Table 2 (pg 11) for proper sizing. To calculate
the chimney's outside diameter, add 3 inches
to the inside diameter.
CHIMNEY HEIGHT
The national Fire protection Association
Standard #211 states: "Chimneys shall extend at
least three feet above the highest point where it
passes through the roof of a building, and at least
two feet higher than any portion of a building
within ten feet." (Fig. 1). Due to the overlap of
the joints, subtract 1 inch from each Chimney
Section's height to calculate installed height.
CHIMNEY ENCLOSURE
REQUIREMENTS
Through Rooms: Interior chimneys shall
be enclosed where they extend through
closets, storage areas, occupied spaces, or
anywhere where the surface of the chimney
could be contacted by persons or combustible
materials (including insulation). The air space
between the outer wall of the chimney and the
enclosure shall be at least 2 inches
Multi-Story: Consult local building code
officials for requirements in your area. The
national Fire protection Association Standard
#211 states: "Factory-built chimneys that
pass through floors of buildings requiring
the protection of vertical openings shall be
enclosed with approved walls having a fire
resistance rating of not less than one hour
NorthlineExpress.com
3 FOOT MINIMUM
ABOVE ROOFLINE
when such chimneys are located in a building
less than 4 stories in height, and not less than
2 hours when such chimneys are located in a
building more than 4 stories in height."
In Canada, except in single-family and two-
family dwellings, chimneys which extend
through another story must have an enclosure
with a fire resistance rating equal to or greater
than that of the floor or roof assembly through
which they pass.
Cold Climates: In cold climates, chimneys
mounted on an outside wall should be
enclosed in a chase. exterior chases reduce
condensation and creosote formation, and
enhance draft. Always maintain a 2" air-space
clearance to combustibles.
FIREPLACE RECOMMENDATIONS
Always follow the fireplace manufacturer's
installation instructions.
Installation: Install your fireplace as described
by the fireplace manufacturer. Be sure to
maintain all required clearances.
Flues: Connect only one fireplace per chimney.
Operation: Follow the fireplace safety manual
for maximum efficiency and safety. Do not over
fire. Any damage to the fireplace or chimney can
possibly void your warranties.
Fuels: Do not burn driftwood, plastic, or
chemically treated wood such as railroad ties.
They are corrosive to your chimney system.
Follow the fireplace manufacturer's instructions
regarding fuels.
http://www.northlineexpress.com
2 FOOT
ABOVE
ANY POINT
WITHIN
10 FOOT
HORIZONTAL
Figure 1
Toll-Free 1-866-667-8454
5