Aplus 240VAC User Manual - Page 14
Browse online or download pdf User Manual for UPS Aplus 240VAC. Aplus 240VAC 17 pages.
SHOR
Inverter short.
OVTP
Over temperature fault.
OVLD
Overload.
SITE
Site fail.
EPO
EPO active.
Please have the following information at hand before calling for service.
1) Model number, serial number
2) Date on which the problem occurred
3) LCD display information, buzzer alarm status
4) Mains power condition, load type and capacity, environment temperature,
ventilation condition
5) The information battery capacity, quantity.
6) Other information for complete description of the problem
Output short circuit.
Remove all the loads.
Turn off the UPS.
Check whether the
output of UPS and
loads is short circuit.
Make sure the short
circuit is removed, and
the UPS has no internal
faults before turning on
again.
Over temperature.
Check the ventilation of
the UPS, check the
ambient temperature
and ventilation.
Overload.
Check the loads and
remove some
non-critical loads.
Check whether some
loads are failed.
Phase and neutral
Rotate mains power
conductor at input of
socket by 180° or
UPS system are
connect UPS system.
reversed.
EPO function is
Plug into the EPO
enabled.
switch.
23
8. Maintenance
8.1 Operation
The UPS system contains no user-serviceable parts.
8.2 Storage
If the batteries are stored in temperate climatic zones, it is recommended to
recharge those batteries every three months for 1~2 hours. It is highly suggested
to shorten the recharging intervals in every two months at locations where
subjects to high temperatures.
24