Apollo XPander XPA-CB-12034-APO Commissioning Manual - Page 6

Browse online or download pdf Commissioning Manual for Smoke Alarm Apollo XPander XPA-CB-12034-APO. Apollo XPander XPA-CB-12034-APO 19 pages. Diversity loop interface module
Also for Apollo XPander XPA-CB-12034-APO: Installation Manual (2 pages), Installation Manual (2 pages)

Apollo XPander XPA-CB-12034-APO Commissioning Manual

Installation

Installation should be carried out in accordance with the radio survey and system design. Siting of the devices
should be in strict accordance with the survey. Failure to do so could result in loss of performance.
The log on procedure (page 8) along with a completed site survey sheet should be sufficient to obtain a stable
working system, the site survey procedure ensures all XPander devices will communicate correctly once installed.
These sheets need to be completed and kept as commissioning and user documentation to comply with BS5839 -
1 section 2-27 and section 5-39 & 40
This guide provides information on features designed to help commission and troubleshoot a system.
Please note: Should building structure change, the site survey will need to be repeated. The system will not
comply to BS 5839 or other national codes if the site survey is not carried out properly and all supporting paper-
work completed (site survey sheet).

Menu - scrolling and selecting

Selecting Menu Options
Menu
A rotary select switch is used for scrolling through the menu and selecting an option. Turn the select switch clock-
wise to scroll down the menu. Turn the switch anti-clockwise to scroll back up the menu. Press the select switch
once to select an option.
The 'Back' button is used to return to the previous menu.
If a menu is selected and no further activity is detected, the menu will 'time out' and the interface will return to
normal operating mode.
Device Status (1.0)
Add New Device (2.0)
Remove Device (3.0)
Interface Status (4.0)
Radio Channels (5.0)
Loop Interface PCB.
Reset
868 MHz Aerial
Button
Connections
RADIO
TX
RX
RESET
Status
POWER
LEDs
FAULT
ISOLATE
WD
LCD Contrast
Loop In, Out and
Adjustment
Screen Connections
© Apollo Fire Detectors Limited 2015
Fault Status (1.1)
Alarm Status (1.2)
Device
Battery Level (1.3)
Address
Signal Level (1.4)
Manual Update (1.5)
Ident (1.6)
Fault Status (4.1)
Background Level (4.2)
Fast Test (4.3)
Ident (4.4)
Currently Used (5.1)
Auto Select (5.2)
Manual Select (5.3)
Front Lid
8 Way loop
Address Switch
Tamper Switch
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7
0V
RX
Help
HELP
TX
3V
Button
Rotary
Control
Back
Button
BACK
LOOP IN
LOOP OUT
-
-
LCD
Screen
6