Apollo SOTERIA UL Installation Manual - Page 2

Browse online or download pdf Installation Manual for Control Unit Apollo SOTERIA UL. Apollo SOTERIA UL 8 pages. Nac module

TECHNICAL INFORMATION COUNT.
Wiring Styles
End-of-Line resistors*
External Supply
Max (NAC)
Max (Speakers)
Note: *A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146
Remarque: * Une résistance de fin de ligne répertoriée UL est disponible chez Apollo, réf. 44251-146
Normal
Normal + Ground Fault
Reverse Polarity
Trouble
Power Supply
Notes: *Notification appliance circuit short/open circuit or group address. Analogue Values need to be tested
with each individual compatible UL listed panel for compatibility.
**These Values are exclusive to monitoring Mode
Remarques: * Court-circuit de circuit d'appareil de notification / circuit ouvert ou adresse de groupe. Les
valeurs analogiques doivent être testées avec chaque panneau homologué UL compatible individuel
pour la compatibilité.
** Ces valeurs sont exclusives au mode de surveillance

INSTALLATION

This product must be installed in accordance with the applicable NFPA standards, local codes and
jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report
an alarm condition. Apollo America Inc. is not responsible for devices which are improperly installed,
maintained and tested.
Before installing this product, check the continuity, polarity and insulation resistance of all wiring. Check
that wiring is in accordance with the fire system drawings and conforms to all applicable local codes
such as NFPA 72.
1.
Mount the electrical box as required and install all cables for termination.
2.
Terminate all cables in compliance with local codes and regulation. Ensure that cable shield/
earth continuity is maintained and no short occurs with the back box(see Fig. 3 and 4 for
wiring instructions)
3.
Set the address on dip switch of the unit as shown on page 4.
4.
Install the wire separator provided.
5.
Gently push the completed assembly towards the mounting box and verify wiring and
address. Align the fixing holes.
6.
Secure the module to the electrical box with provided screws. Do not over tighten screws.
7.
Place the face plate over the module and secure with provided screws.
8.
Commission the module.
Notification Appliance Circuit (NAC)
Supervised power limited Class A and Class B
47k Ω
Connected between Vext+ and Vext- Monitored
input (DC Voltage Supplies Only)
Regulated 24V DC, 2A. Use a regulated power
limited dc supply that is listed for fire protection
applications. The maximum number of connected
devices must be within the output rating.
70.7V rms, 500 mA with wire supervision
capability as per NFPA requirements. The
speakers used must be UL listed for fire
protection applications.
Refer to fire control panel literature for details on
how to achieve audio and visual synchronization.
Analogue Values
16
19
15**
4*
2**
2