4EVAC Compact 500 Operation Manual - Page 8
Browse online or download pdf Operation Manual for Safety Equipment 4EVAC Compact 500. 4EVAC Compact 500 15 pages. Voice evacuation system
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4EVAC Compact 500 operation manual
Continuous:
At least one device from the network is missing.
4.1.7. Zone indicators
Zone indicators are strictly related to the corresponding zone button. If a button is not attached to any
zone, then zone indicators for this button are disabled.
4.1.7.1. Red
Indicates that the zone is in EVAC condition, where the zone is occupied by one of following audio signals:
Continuous: LIVE EVAC
Blinking slow: EVAC Message.
4.1.7.2. Yellow
Indicates that the zone is transmitting an ALERT message, and/or is in fault state
Continuous: Zone fault (fault of any line / amplifier included in this zone)
Blinking slow: Zone is transmitting ALERT Message.
4.1.7.3. Blue
Zone busy / zone selection.
Continuous: indicates that the zone is manually selected via zone selection button on local panel
Blinking fast: the zone is occupied by audio signal, but is in SILENCE mode (triggered by SILENCE
input or manual SILENCE button)
Blinking slow: indicates that the zone is currently transmitting an audio signal (except BGM).
Page 8 of 15
Author:
Zone A
Manual zone control
DD