b. IOMOD HT configuration with PuTTY terminal
Configuration of IOMOD device is done through CLI (Command Line Interface) on virtual
COM port. Drivers needed for MS Windows to install VCOM will be provided. To open up CLI
simply connect to specific V-COM port with terminal software (advised to use PuTTY terminal
software. If other software is being used, user might need to send <return> symbol after
each command). When connected user should immediately see main screen:
Navigation is performed by sending number to terminal. User then proceeds by following
further on-screen instructions. For example, to set Baudrate, press [2] to enter Boudrate
screen; press [1] to edit; enter new configuration; press [RETURN] to save, or [ESC] to
cancel changes. When done, press [0] (exit) before disconnecting device. Default values is
set by pressing [7] on main screen, and confirming changes [1].
If accidentally closed the terminal window, user can connect terminal program again, and
press any key on keyboard to show up main menu.
V0.6 | ELSETA | IOMOD HT configuration with PuTTY terminal
IOMOD HT
12/17/2015
9
c. Main Menu
Menu Name
Function
1.
Slave Address
Modbus Slave
address / ID
2.
Modbus
Modbus Baudrate
Baudrate
3.
Data, Stop and
Chooses Stop
Parity bits
and parity bits to
use
4.
RS485
RS485 120 Ohms
Terminating
Terminating
Resistor
Resistor
5.
Relay #1
Active mode and
settings
active range
6.
Relay #2
Active mode and
settings
active range
7.
Set Default
Sets Default
Settings
Settings
8.
Firmware
Mass Storage
Upgrade
Device Firmware
Upgrade
0.
Exit
Exit
and disconnect
V0.6 | ELSETA | IOMOD HT configuration with PuTTY terminal
IOMOD HT
12/17/2015
Default
Values
Values
1-247
(default: 1)
100 - 256000
(default: 9600)
(default: 8N1)
0 - 1 (off/on)
(default: 0)
Active mode: 1 –Relay
(default: 0)
disabled;
2- Temperature active
3- Humidity active;
active range:
-10 to 60 (temperature)
and 0 to 100 (humidity)
Active mode: 1 –Relay
(default: 0)
disabled;
2- Temperature active
3- Humidity active;
active range:
-10 to 60 (temperature)
and 0 to 100 (humidity)
(1 to confirm, 0 to
-
cancel)
(1 to confirm, 0 to
-
cancel)
-
-
10