6.5 SENSOR DATA

ADDRESS NAME
20480
Max Temp 1
20481
Max Temp 2
20482
Max Temp 3
20483
Max Temp 4
20484
Temp 1
20485
Temp 2
20486
Temp 3
20487
Temp 4

7. TECHNICAL SPECIFICATIONS

Supply Input:
19-400VDC (85-305VAC)
Measuring Inputs:
4 x PT100 (3 terminals)
Accuracy:
1% + 1 digit
Measurement Range: -40 to +250°C
Power Consumption: < 4 VA
Relay Outputs: 5A @ 250V AC
Serial Port:
Signal type: RS-485
Protocol: Modbus RTU
Data Rate: 2400-115200b, adjustable
Isolation: 1000V AC, 1 minute
Operating Temperature range:
-20°C to +70 °C (-4°F to 158°F)
Max Relative Humidity:
95% non condensing
Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: [email protected] http: www.datakom.com.tr
DESCRIPTION
Channel 1 Maximum Temp.
Channel 2 Maximum Temp.
Channel 3 Maximum Temp.
Channel 4 Maximum Temp.
Channel 1 Actual Temperature
Channel 2 Actual Temperature
Channel 3 Actual Temperature
Channel 4 Actual Temperature
DATAKOM Elektronics Inc.
-19-
LENGTH R/W
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
16 BIT
R-O
Protection:
IP 65 (front panel, with gasket)
IP 30 (back panel)
Enclosure:
Flame retardant, ROHS compliant,
high temperature ABS/PC (UL94-V0)
Installation:
Panel mount, rear retaining plastic
brackets.
Dimensions:
102x102x53mm (WxHxD)
Panel Cut-out: 92x92mm
Weight: 200 gr (approx)
EU Directives:
2014/35/EC (LVD)
2014/30/EC (EMC)
V-3.0
(14.09.2016)
TYPE
X
unsigned
1
word
unsigned
1
word
unsigned
1
word
unsigned
1
word
unsigned
1
word
unsigned
1
word
unsigned
1
word
unsigned
1
word
Reference
Standards:
EN 61010 (safety)
EN 61326 (EMC)