Individual operation
Manual individual operation of the drives can take place via the integrated Up/Down
buttons at the device or via unlocked double buttons (extension inputs). The movement
mode can be stopped via both buttons (
movement.
LED signals during manual control:
During movement:
Runtime reached
without interruption:
Intermediate position
reached:
Manual operation can be set to "Standard mode" or "Comfort mode":
Standard mode (default)
•
If a button is pressed for less than 1 second, the drive will move in a step-by-step
fashion. This allows, for example, slats to be positioned precisely.
•
If a button is held for longer than 1 second, the drive moves to its final position
(switching off after 240 seconds of maximum runtime)
This is how you set the Standard mode:
•
Press the
button on the channel to be set for 5 seconds and then additionally the
button for longer than 1 second
•
To confirm the On LED on the channel flashes 5 times
Comfort mode:
•
If a button is held for less than 0.3 seconds, the drive moves to its final position
(switching off after 240 seconds of maximum runtime)
•
If a button is held for longer than 0.3 seconds, but less than 2 seconds, the drive
moves only while the button is pressed and stops immediately when it is released
(deadman function)
•
If a button is held for longer than 2 seconds, the drive moves to its final position
(switching off after 240 seconds of maximum runtime)
This is how you set the Comfort mode:
•
Press the
button on the channel to be set for 5 seconds and then additionally the
button for longer than 1 second
•
To confirm the Off LED on the channel flashes 5 times
Individual movement position
The IMSG-UC-4H can store one movement position for each connected drive. This allows
fast and uncomplicated movement to a position that is needed often (e.g. a shutter
position or the partial opening of a window).
Motor control unit IMSG-UC-4H • Status 30/06/2010 • Subject to technical changes. Errors excepted.
Channel LED in the direction of movement flashes every second
LED for the direction travelled remains on
LEDs off
or
), regardless of the current direction of
3