elsner elektronik WS1000 Style Brief Instruction - Page 2

Browse online or download pdf Brief Instruction for Control Unit elsner elektronik WS1000 Style. elsner elektronik WS1000 Style 2 pages. Connect control system
Also for elsner elektronik WS1000 Style: First Steps (2 pages), First Steps (2 pages), Manual (2 pages), Assembly Instructions (2 pages), Manual (20 pages), Brief Instruction (2 pages)

elsner elektronik WS1000 Style Brief Instruction
Technical specifications Control Unit WS1000 Style
Housing
Glass, plastic material
Colours
• White/grey
• Dark grey/black
Mounting
Flush/cavity wall
Dimensions
Display front approx. 1270× 185 (W × H, mm),
mounting depth approx. 9 mm,
concealed box approx. 254 × 171 × 85 (W × H × D, mm)
Ambient temperature
Operation 0...+55°C, Storage -30...+70°C
Ambient humidity
5...95% RH, avoid bedewing
Operating voltage
230 V AC, 50 Hz
Power consumption
Stand-by max. 17 W
Loading capacity
230 V outputs:
drive outputs
per motor output, max. 400 W,
total max. 1.5 kW
Potential-free outputs (PF model):
per motor output max. 5 A / 230 V
Frequency
868.2 MHz
wireless channels
Protection category
IP 20
The product conforms with the provisions of EU directives.
Connection diagrams
Drive and MF outputs WS1000 Style (60201-60204, 60206-60209):
max. 400 W per motor output,
total max. 1.5 kW for all motor outputs
Drive and MF outputs WS1000 Style-PF (60214):
per motor output max. 5 A / 230 V
Motors with different voltages may be operated at the drive outputs (230 V AC and
low voltages SELV). The low voltage drives still correspond to the SELV specifica-
tions.
230 V and SELV must not be mixed at adjacent multifunction outputs (1 and 2 or 3
and 4). A mixed connection does not correspond to the SELV specifications. Either
230 V or extra-safety voltages are permitted here.
Mounting of WS1000 Style
E.g. it is possible to connection SELV to MF outputs 1 and 2 and 230 V to MF out-
puts 3 and 4 (or vice versa).
Inputs WS1000:
Mounting of WS1000 Style • Version: 30.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Connection examples for multifunctional outputs
Connecting 230 V consumers to MF outputs
multifunctional outputs 1-4 WS1000 Color/Style
multifunctional outputs 1-2 WS1 Color/Style
MF output 1
MF output 2
MF output 3
neutral conductor
Connecting low-voltage consumers and potential-free contacts to MF
outputs
multifunctional outputs 1-4 WS1000 Color/Style
multifunctional outputs 1-2 WS1 Color/Style
MF output 1
MF output 2
e.g. 24 V (ext.power supply)
2
MF output 4
MF output 3
MF output 4
signal contact for e.g.
rain / wind / frost /
smoke detector / alarm
thermostat
replacement
(on-site)