COOK HMD Installation, Operation And Maintenance Manual - Page 5
Browse online or download pdf Installation, Operation And Maintenance Manual for Air Handlers COOK HMD. COOK HMD 17 pages. Heated makeup direct: a direct fire make-up air unit
Gas
1. Check the supply gas pressure and compare it with
the unit's nameplate pressure requirements. Adjust
the supply regulator as needed until the supply gas
pressure is within the specified range (see below).
The nameplate is located on the outside of the unit
on the control panel side.
2. Check the settings on the optional high and low gas
pressure switches. The high pressure setting is typi-
cally 8 inches wc (2 kPa) and the low pressure is set-
ting is typically 3 inches wc (0.7 kPa). The switches
are set at the factory and should not need adjust-
ment. Adjust the setting only if needed. The pur-
pose of the high and low gas pressure switches is
to automatically shut down the burner if the inlet gas
pressure is too low for the burner to safely light, or
if the manifold pressure is too high for the burner to
operate properly. Proper air velocity over the burner
is critical on direct fired gas units. If the air velocity
is not within the unit specifications, the unit will not
operate efficiently, may have sporadic shutdowns,
and may produce excessive carbon monoxide (CO)
or other gases.
Control Panel Parts
1. Contactor
2. Overload
3. Three phase
transformer #A
4. 120 - 24v
transformer #B
5. Ignition control
6. High Temp Overload
Control Panel
23
16
18
17
HMD IO&M
7. Mild weather thermostat to
damper
8. Damper motor
9. Terminal blocks
10. Circuit breaker
11. Override switch
12. 120v spark ignitor
13. Pressure sensing probe (high)
14. Pressure sensing probe (low)
1
2
3
9
10
11
19
Testing Inspection
All components of this or any other gas-fired heating
unit must be leak tested prior to placing the unit into op-
eration. The factory piping has been checked for leaks
but should be rechecked due to shipping & installation
issues. The field-installed shutoff valve should also be
checked.
A soap & water solution should be used to perform this
test.
Never test for gas leaks with a flame.
When leak testing pressures that are less than or equal
to 14 in. wc (3.5 kPa), first close the field-installed shut-
off valve to isolate the unit from gas supply line.
When leak testing pressures that are more than 14 in.
wc (3.5 kPa), close the field-installed shutoff valve, dis-
connect the furnace & gas train from the gas supply line
& plug the supply line before testing.
All piping should be clean & free of any foreign matter,
which may damage the valves, regulators or burner.
4
5
12
13
14
20
5
15. Temperature controller
16. Thermostat to blower
17. Safety Shut off valve
18. Pressure gauge
19. Gas valve
20. Modulating gas valve
21. Pressure gauge
22. Safety Shut off valve
23. Optional V.F.D. here
7
6
8
15
21
22
B51242-002