SPECIFICATION
Input Power:
Not Supervised
Alarm Dry Contact Rating:
Alarm Door Close Warning:
Brake Release (Dry Contact):
Fuse:
24V input power can be 24VDC or 24VAC or 24VDC from an approved UL1481 regulated power
supply.
18-gauge wire recommended.
For "Indoor Dry" location use only.
Close warning power is provided for less than a minute. Any UL Listed audible or visual device
may be used if the 24VDC input is powered by a UL1481 regulated and power limited power
supply.
Optional: Activation/connection of UL approved fusible links.
Voltage
Frequency
120VAC
24VAC
24VDC
*Note: Amp value is during alarm condition with 1A load warning
connected.
24VDC, 0.5A, Not Supervised
24VDC @Max. 1A, Resistive, Special Application (see below),
Common, Not Supervised
Rating: 24VAC/VDC, 2A Max., Resistive Load, Common,
Not Supervised
F1: 3A@250V, Slo-Blo Type
F2: 1A@250V, Fast-Act Type
2
Standby
50 Hz
0.3A
60 Hz
0.3A
50 Hz
1.5A
60 Hz
1.5A
-
0.6A
M100 FireGard
Alarm*
0.4A
0.4A
1.8A
1.8A
1.2A
TM
Chain & Crank