Technische Daten
Isolationskoordination nach DIN VDE 0110 T1
Bemessungsspannung ...................................................AC 250 V
Bemessungsstoßspannung/Verschmutzungsgrad ..........2,5 kV/3
Spannungsbereiche
Versorgungsspannung U
............ AC/DC 60...264 V, 50...60 Hz
S
Sicherung ................................................... empfohlen: 6 A träge
Eigenverbrauch ..........................................ca. 5,8 VA bei AC 60 V
.................................................................ca. 8,5 VA bei AC 264 V
Überwachung des Differenzstroms
Ansprechwert Differenzstrom ......................................................
............................................ einstellbar 0,1...1 A bzw. 1...10 A
Ansprechabweichung .............................................. +0...-25 %
Ansprechverzögerung ..................................einstellbar 0,1...2 s
Toleranz der Ansprechverzögerung ..................................±20 %
Dauerkurzschlussstrom .......................................................200 A
.............................................................................. 2 500 A für 2 s
Arbeitsweise ..........................................Fehlerspeicherverhalten
Überwachung des Erdungswiderstandes
Ansprechwert Spannungsmessung .......... einstellbar 20...400 V
Ansprechabweichung ......................................................± 10 %
Ansprechwert Erdungswiderstandsmessung bei U
Ansprechabweichung .....+5...-2 % des Ankoppelwiderstandes
Ansprechzeit ............................................................... 5 s ±20 %
Arbeitsweise ..........................................Fehlerspeicherverhalten
Eingänge
Anschluss zum Differenzstromwandler:
Einzeldraht 0,75 mm
(AWG 18) ................................ bis 1 m (3')
2
Einzeldraht verdrillt 0,75 mm
Schirmleitung 0,75 mm
2
(AWG 18) (Schirm an PE)
.................................................................. 10...25 m (30...75')
Anschluss zur Melde- und Prüfkombination RI2000NC:
Einzeldraht 0,75 mm2 (AWG 18) .................. 0...10 m (0...30')
Ausgänge
Schaltglieder (Alarmrelais) .........................................2 Wechsler
Kontaktbemessungsspannung ....................... AC 250 V/DC 300 V
Einschaltvermögen ...................................................... AC/DC 5 A
Ausschaltvermögen ...............................................AC/DC 2/0,2 A
Zulässige Schaltzahl ...................................... 12 000 Schaltspiele
Arbeitsweise Schaltglieder (Alarmrelais), umschaltbar: ..............
............................... Arbeitsstromverhalten/Ruhestromverhalten
Schaltglieder (GFA, NRA) ........................................... 2 Schließer
Kontaktbemessungsspannung ....................... AC 250 V/DC 300 V
Einschaltvermögen ...................................................... AC/DC 5 A
Ausschaltvermögen ...............................................AC/DC 2/0,2 A
Zulässige Schaltzahl ...................................... 12 000 Schaltspiele
= 0 V ....2 kΩ
N
2
(AWG 18) ...... 1...10 m (3...30')
Technical data
Insulation coordination acc. to IEC 60664-1
Rated insulation voltage ................................................AC 250 V
Rated impulse withstand voltage/pollution degree .......2.5 kV/3
Voltage ranges
Supply voltage U
........................ AC/DC 60...264 V, 50...60 Hz
S
Fuse ............................................... recommended: 6 A slow fuse
Power consumption .............................approx. 5.8 VA at AC 60 V
...........................................................approx. 8.5 VA at AC 264 V
Residual current monitoring
Response value, residual current .................................................
................................. adjustable 0.1...1 A respectively 1...10 A
Accuracy ................................................................... +0...-25 %
Response delay ............................................adjustable 0.1...2 s
Accuracy of response delay ...............................................±20 %
Continuous short circuit current ..........................................200 A
.............................................................................. 2 500 A for 2 s
Operating mode ..............................................................latching
Ground conductor monitoring
Response value, voltage measurement ... adjustable 20...400 V
Accuracy ...........................................................................± 10 %
Response value, neutral grounding resistor at U
Accuracy ............................+5...-2 % of the coupling resistance
Response time ............................................................ 5 s ±20 %
Operating mode ..............................................................latching
Inputs
Connection to the residual current transformer:
Single wire 0.75 mm
(AWG 18) ............................ up to 1 m (3')
2
Single wire, twisted 0.75 mm
Shielded cable 0.75 mm
2
(AWG 18) (shield to Ground)
.................................................................. 10...25 m (30...75')
Connection to the remote alarm indicator and operator panel
RI2000NC:
Single wire 0.75 mm2 (AWG 18)................... 0...10 m (0...30')
Outputs
Switching elements (alarm relay) .............2 changeover contacts
Rated contact voltage .................................... AC 250 V/DC 300 V
Limited making capacity .............................................. AC/DC 5 A
Limited breaking capacity ......................................AC/DC 2/0.2 A
Permissible number of operations ..........................12 000 cycles
Operating mode, alarm relay, selectable: ....................................
.......................................................N/O operation/N/C operation
Switching elements (GFA, NRA) ............................. 2 NO contacts
Rated contact voltage .................................... AC 250 V/DC 300 V
Limited making capacity .............................................. AC/DC 5 A
Limited breaking capacity ......................................AC/DC 2/0.2 A
Permissible number of operations ..........................12 000 cycles
RC48N_D00426_00_M_DEEN / 08.2020
= 0 V .......2 kΩ
N
2
(AWG 18)...... 1...10 m (3...30')
9