GAC IGC700 Series Manual - Page 16
Browse online or download pdf Manual for Controller GAC IGC700 Series. GAC IGC700 Series 18 pages. Integral governor control
L9
GAIN
L8
STABILITY
DERIVATIVE
10
9
8
7
6
5
L7
4
3
2
1
B8
0
OVERNORS
MERICA
ORP.
MADE IN USA
B7
B6
B5
Table 2 - Description of Front Panel Buttons
Button
Button Label
Stops the engine. Will also stop any
B1
Stop
start cycle.
B2
AUX
Turns AUX Driver on or off.
B3
Fault
Clears all faults in the IGC.
Initiates Crank Cycle. Pressing and
B4
Start
holding this button will bypass Crank
Cycle and begin cranking.
Used to enter any 4-digit number.
B5
Enter
DO NOT use with +/- buttons.
Pressing and Holding until Run/Setup
B6
Run
LED stops flashing saves changes.
Press and Hold this button until
Run/Setup LED starts to flash. Enter
4-digit access code and press Enter
B7
Setup
button. Note: IF IGC is running the
Run/Setup LED will not flash. You
can however proceed
Press this button sequentially to access
the parameter you want to adjust.
Each time you depress this button, the
B8
Menu
next LED will come on indicating that
you are in menu selection mode. Also,
the Fault LED will come on indicating
menu selection mode. .
L2
L1
L3
ENGINE RUN
RUN / SETUP
TEMP. °C
FAULT
OIL PRESS.
CHARGE FAIL
ERROR 1
ERROR 2
ERROR 3
ERROR 4
IP54
B3
B4
Description
L4
L5
Diagram 2 – See Tables 2 & 3
L6
for Description of Front Panel Buttons and LED's
B1
B2
Table 3 - Description of Front Panel LED's
LED
LED Label
L1
Run/Setup
L2
Engine Run
Engine
L3
Temperature
L4
Oil Pressure
L5
Charge Fail
Error
L6
1,2,3 & 4
L7
Bar Graph
Gain, Stability
L8
& Derivative
L9
Fault
16
Description
Steady ON = IGC is operating;
Flashing = SETUP mode.
ON = Engine speed has exceeded
Crank Termination setting.
ON= Engine temperature has
exceeded Temperature setting.
ON = Engine oil pressure has
exceeded Oil Pressure setting.
ON = Batteries has failed to charge
(failed alternator, broken belt, etc.).
User Configurable. Use with any
of the configurable inputs.
(R, S, T, W, X, Y & Z)
During Crank Cycle the graph will
sequence from 1 to 10 (0-100%)
indicating preheat time and pause
between crank time. In SETUP
mode, shows 0 to 100% of the
parameter value and depending on
the parameter will flash a 4-digit
code to show exact value of that
parameter.
These LED's will come on
individually when their respective
parameters are being accessed for
adjustment. The Derivative LED
also lights during the Cranking
Cycle.
ON = Overspeed has been tripped -
OR - IGC Self-test failed (bad
checksum or invalid configuration
parameter) - OR - IGC stopped by
local Stop button when Remote
Start/Stop is latched on.