GAC EEG6550 Series Manual - Page 8

Browse online or download pdf Manual for Switch GAC EEG6550 Series. GAC EEG6550 Series 13 pages. Enhanced electronic governor

GAC EEG6550 Series Manual
8
PRE-START SET-UP & qUICkSET PARAMETERS
Set the following parameters before starting the engine:
#TeeTH
Input the Number of Teeth on the Flywheel. This can not
be changed while engine is running.
cranK
Input the Crank Termination (RPM)
SPeeD
Input the Fixed Speed of the Engine (RPM)
over SPeeD *
Range: 400 - 6000 RPM
Default: 2000 RPM
RPM to automatically shutoff the
actuator
SPeeD ramP
Range: 25 - 2000
Default: 300
Rate at which speed changes from
idle to set speed and back, or rate
change in variable speed mode.
STarT fUel
Range: 0 - 100 %
Default: 100 %
Initial actuator position at the start of
cranking
SPeeD *
Range: 0-6000 RPM (fixed)
0-6000 RPM (droop)
Default: 1500 RPM (fixed)
50 RPM (droop)
Operating speed of engine
GaIn
Range: 1 - 100, 100 = Max Gain
Default: 50 (rated)
: 10 (idle)
Proportional (P) set point of the PID
control at operating SPEED and IDLE
* 12 KHz MAx
aDjUSTaBle QUIKSeT ParameTerS
#TeeTH
Range: 60 - 250
Default: 120
Number of teeth on flywheel
v.SPeeD *
Range: 0-6000 RPM (vspd) 0-120 Hz (trim)
Default: 1800 RPM (vspd) : 0 Hz (trim)
Maximum speed change allowed from trim
input
DrooP%
Range: 0 - 25.0 %
Default: 5.0 %
Droop to apply under maximum load
(based on current of actuator)
IDle *
Range: 150 - 1500 RPM
Default: 900 RPM
Speed of engine when IDLE input is closed
STaBIlITY
Range: 1 - 100, 100 = fastest response
Default: 50
Integral (I) set point of the PID control
8
cranK *
Range: 100 - 1000 RPM
Default: 400 RPM
RPM which EEG switches from starting fuel
limit to fuel limit
locKeD
Range: OFF, ON
Default: OFF
Enables Manual/Auto locking of display. Press
and hold UP and DOWN arrows
simultaneously for 3 seconds to UNLOCK or
LOCK the display.
fUel ramP
Range: 1 - 100 % / Sec.
Default: 10 %
Actuator position increase in percent per sec-
ond from cranking to low idle speed, starting
from the Start Fuel position
fUel lIm
Range: 0 - 100%
Default: 100%
Maximum actuator percentage allowed
DeaDTIme
Range: LOW, HI
Default: HI
Derivative (D) set point of the PID control
EEG6550 Enhanced Electronic Governor 5-2020-A1
Governors America Corp. © 2020 Copyright All Rights Reserved
PIB1118