HI-FOG 1900 Identification And Correction Procedure - Page 4
Browse online or download pdf Identification And Correction Procedure for Irrigation System HI-FOG 1900. HI-FOG 1900 18 pages. A1000 type assembly body with stop valve
18/09/2017
3.
Affected and other Assembly Bodies
The risk and the related corrective action required are relevant only for HI-FOG
1900 sprinklers (see Chapter 2 to identify) when installed in some A1000 types
Assembly Body, which contain an internal stop valve.
HI-FOG sprinkler installed in other types of Assembly Body require none of the
actions referred to by this document.
To differentiate the A1000 Assembly Body from other Assembly Body types note
the following:
a.
With the A1000 type Assembly body there is no gap between the HI-FOG
1900 sprinkler and the cover plate when the HI-FOG 1900 sprinkler is
installed (see Figure 01). The cover plate (see Figure 01) of A1000
Assembly body types is held in place by the sprinkler.
b.
The A2000 Assembly body type is suitable only for HI-FOG 2000 sprinklers
(see Figure 02 for sprinkler types).
c.
A HI-FOG 1900 sprinkler installed in an AB type Assembly body would either
leave a 2 – 3 mm gap between the top of the sprinkler and the cover plate,
or would have an adaptor ring filling the gap.
See Figure 03 for AB types below – left half without adaptor ring and right
half with adaptor ring. The cover plate of AB type is connected to the
Mounting Adaptor with a lock ring.
d.
The C type the installation with HI-FOG 1900 sprinkler would leave a narrow
gap between the top of the sprinkler and the cover plate - The cover plate of
C type is snapped directly to the Assembly body.
A1000 types
Notes:
- Cover plate
supported by the
sprinkler : no gap
Action Required
for HI-FOG 1900
Document number 0003301084
A2000 types
Notes:
Notes:
- Cover plate
- Cover plate
supported by the
sprinkler : not
applicable for HF
1900
No Action Required
Figure 03 : Assembly Body types
Ver. A
AB types
Notes:
- Cover plate
supported by lock
snapped to the
ring : gap or
Assembly Body :
adaptor ring
gap
C types