ADEMCO 4110XM Installation Instructions Manual - Page 10

Browse online or download pdf Installation Instructions Manual for Security System ADEMCO 4110XM. ADEMCO 4110XM 20 pages.

ADEMCO 4110XM Installation Instructions Manual

11. Install Wireless Transmitters

• Select a House ID (all transmitters must be set to the same House ID as you will program
into the system). To determine a House ID that is not being used in a nearby system, use
the House ID Sniffer Mode ( see Section 5: TESTING THE SYSTEM for further
instructions on using House ID Sniffer Mode).
• Determine what zone response type each transmitter will represent.
• Select each transmitter's zone number according to its zone response type (use the chart
below).
ZONE NUMBER (RF XMTR ID)
10-13
14-29
30-43
44, 45
46, 47
• Set DIP switches on transmitters (according to each transmitter's instructions) for the zone
numbers and House ID selected (see DIP Switch Settings for Wireless Devices on page 17 of
this manual. Do not set two transmitters for the same zone number.
• Mark each transmitter's zone number so you can identify it easily when mounting.
• Program House ID and transmitter zone numbers into the system (see program fields *24
and *76 thru *92).
Do not permanently mount transmitters until transmission from each location has been
verified (see Section 5: TESTING THE SYSTEM for instructions on performing the Go/No Go
Test Mode.
––––––––––––––––––––––– WIRING GUIDELINES –––––––––––––––––
Wire Size
#22
#20
#18
#16
*
Includes Keypads, RF Receiver, and alarm devices requiring separate power.
Example: If you have two motion detectors that draw a total of 44 mA, and you are
using #20 AWG wire, the distance from the control panel Aux + and -
terminals to the last device can be up to 750 ft.
IMPORTANT
ZONE TYPE
ENTRY/EXIT, Burg.
PERIMETER, Burg.
INT/FOLLOWER, Burg.
INT w/DELAY, Burg.
PERIMETER, Burg.
Aux Power Wire Run Chart
TOTAL CURRENT DRAWN BY ALL DEVICES* CONNECTED TO A SINGLE
50 mA or less
51 - 100 mA
500 ft (152m)
250 ft (76m)
750 ft (228.6m)
380 ft (116m)
1300 ft (396m)
650 ft (198m)
1500 ft (457m)
1000 ft (305m)
The combined length of all wire runs for devices connected to the
keypad data lines must not exceed 1500 feet (457m) when unshielded
quad conductor cable is used (750 feet if shielded cable is used). This
restriction is due to the capacitive effect on the data lines when quad
cable is used.
Transformer Wiring Table
Distance of Transformer
From the Control Panel
Up to 50 feet
50–100 feet
100–250 feet
-10-
RF XMTR ID
48-55
56-61
62
63
WIRE RUN
101- 300 mA
80 ft (24m)
130 ft (39.6m)
220 ft (67m)
330 ft (100.5m)
Wire Gauge
To Use
# 20
# 18
# 16
ZONE TYPE
FIRE
TROUBLE BY DAY/
ALARM BY NITE, Burg.
24 hr. (audible)
Programmed by field *92
301 - 500 mA
50 ft (15m)
80 ft (24m)
130 ft (39.6m)
200 ft (70m)