75F Pressure Controller Installation & Operation Instructions - Page 2
Browse online or download pdf Installation & Operation Instructions for Accessories 75F Pressure Controller. 75F Pressure Controller 7 pages. Pressure sensor package
•
Install in accordance with all state and local codes.
|
FEATURES
•
Monitoring of differential pressure between barometric and
indoor pressure.
•
When used in conjunction with the 75F Outside Air
Optimization Package, pressure control is possible.
|
SPECIFICATIONS
75F Pressure Controller
•
Supply Voltage: 24VAC
•
Input: 0-10VDC
•
Operating Environment:
•
Enclosure: Rainproof type 3R non-metallic enclosure
A/DP2 Series Pressure Sensor
•
Supply Voltage: 24VAC
•
Output: 0-10VDC signal
•
Range: +/-0.25"W.C
•
Accuracy: +/-0.8%
•
Operating Environment: 14 to 140F, 0-92% R.H.
non-condensing
•
Enclosure: UL94-V0 rated, flame retardant ABS, RoHS
|
MOUNTING
Roof
Ceiling
Fig.2
41°F – 122°F
www.75f.io
888.590.8995 x2