ADEMCO Ademco VISTA-20P Programming Manual
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries shown in dashed
boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition,
where noted, certain fields have special settings when used with the VISTA-20PSIA/VISTA-15PSIA (indicated by
borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
∗ ∗ ∗ ∗ 20
Installer Code
4 digits, 0–9
∗ ∗ ∗ ∗ 21
Quick Arm Enable
0 = no; 1 = yes
∗ ∗ ∗ ∗ 22
RF Jam Option
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
∗ ∗ ∗ ∗ 23
Quick (Forced) Bypass
0 = no quick bypass UL: must be "0"
1 = allow quick bypass (code + [6] + [#] )
∗ ∗ ∗ ∗ 24
RF House ID Code
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
∗ ∗ ∗ ∗ 26
Chime By Zone
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
∗ ∗ ∗ ∗ 27
Powerline Carrier Device (X–10)

House Code

0 = A; 1 = B; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I; 9 = J;
#10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
UL: not for fire or UL installations
∗ ∗ ∗ ∗ 28
Access Code For Phone Module
00 = disable;
1st digit: enter 1–9; 2nd digit: enter # + 11 for " ✱ ", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
∗ ∗ ∗ ∗ 29
Long Range Radio Output
0 = disable; 1 = enable
∗ ∗ ∗ ∗ 31
Single Alarm Sounding Per Zone
0 = unlimited sounding; 1 = one alarm sounding per zone
V20PSIA/V15PSIA:
If "0" selected, "alarm sounding per zone" will be
the same as the "number of reports in armed period" set in field *93 (1
if one report, 2 if 2 reports, unlimited for zones in zone list 7).
∗ ∗ ∗ ∗ 32
Fire Alarm Sounder Timeout
0 = sound stops at timeout; 1 = no timeout UL: must be "1" for fire install.
∗ ∗ ∗ ∗ 33
Alarm Sounder (Bell) Timeout
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
∗ ∗ ∗ ∗ 34
Exit Delay
00 - 96 = 0 - 96 secs; 97 = 120 secs
SIA Guidelines: minimum exit delay is 45 seconds
V20PSIA/V15PSIA:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements.
∗ ∗ ∗ ∗ 35
Entry Delay #1
Common zones use same delay as partition 1.
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.

PROGRAMMING FORM

[4112]
|
|
|
[0,0]
Part. 1 Part.2
[0,0]
Part. 1 Part. 2
|
|
[00,00,00]
Part. 1 Part. 2
Common
[0]
[0]
[00]
|
(Partition 1 only)
[0]
[0]
[0]
[1]
[60,60]
|
Part. 1
Part. 2
Common zones use part. 1 delay.
[30,30]
|
Part. 1
Part. 2
∗ ∗ ∗ ∗ 36
Entry Delay #2
See *35 Entry Delay 1 for entries.
∗ ∗ ∗ ∗ 37
Audible Exit Warning
0 = no; 1 = yes (SIA Guidelines: must be enabled)
V20PSIA/V15PSIA:
[0]
∗ ∗ ∗ ∗ 38
Confirmation Of Arming Ding
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
UL: must be "1" for UL Commercial Burglar Alarm inst.
∗ ∗ ∗ ∗ 39
Power Up In Previous State
|
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be "1" SIA Guidelines: must be "1"
DIALER PROGRAMMING ( ✱ 40 – ✱ 42)
Do not fill unused spaces. Enter 0–9; #+11 for ' ✱ '; #+12 for '#'; #+13 for a 2-
second pause. If fewer than the maximum digits entered, exit the field by
pressing [✶]. The next data field number is displayed.
∗ ∗ ∗ ∗ 40
PABX Access Code or
Call Waiting Disable
press ✱40✱. If call waiting is used, enter call waiting disable digits "∗
(#+11) 70" plus "# + 13" (pause).
NOTES: 1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V20PSIA/V15PSIA:
as described above, and also set Call Waiting Disable option in field *91.
∗ ∗ ∗ ∗ 41
Primary Phone No.
|
|
|
|
∗ ∗ ∗ ∗ 42
Second Phone No.
|
|
|
|
Enter up to 20 digits. To clear entries, press ✱ 41 ✱ or ✱ 42 ✱ respectively .
NOTE: For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; #+15 for F. Enter [ ✱ ] as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are
used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
∗ ∗ ∗ ∗ 43
Partition 1 Primary Acct. No.
| | | /
| | | | |
chosen in *48 Report Format. See box above. To clear entries, press * 43 *.
∗ ∗ ∗ ∗ 44
Part. 1 Secondary Acct. No.
| | | /
| | | | |
|
∗ ∗ ∗ ∗ 45
Partition 2 Primary Acct. No.
| | | /
| | | | |
∗ ∗ ∗ ∗ 46
Partition 2 Secondary Acct. No.
| | | /
| | | | |
∗ ∗ ∗ ∗ 47
Phone System Select
If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial;
|
if Cent. Sta. is on a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
∗ ∗ ∗ ∗ 48
Report Format
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID® REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
– 3 –
V20PSIA/V15PSIA
[30,30]
Part. 1
[1,1]
feature always enabled; field does not exist
[0,0]
Enter up to 6 digits. To clear entries,
If call waiting is used, enter call waiting disable digits
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[FFFFFFFFFF] Enter 4 or 10 digits, as
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 44 * .
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 45 * .
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 46 * .
[77]
primary secondary
with heavy
|
|
Part. 2
Part. 1 Part. 2
Part. 1 Part. 2
[1]
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[1]