Type 21
Arm-Away
(BR only)
Type 22
Disarm
(BR only)
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 77
Keyswitch
Type 81
AAV Monitor Zone
Types 90-91
Installer Defined
*The system can still be armed when these zone types are in a faulted condition.
Schedules
(installer code + [#] + [6] [4]; master code can only access schedules 01-04 and events 00-07)
No.
Event
Device No.
(see list below)
for "01" events:
enter 01-08, 17,18 enter 1-8
01
02
03
04
05
06
07
08**
[11]
Events:
Master/Installer
00 = clear event
01 = device on/off
02 = user access
03 = latch key report
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
Periodic Test Report Schedule Notes
** After the initial upload, a test report schedule is automatically programmed in schedule 8 (set with values in brackets).
† Test report start time is 12 hours after the time set locally or, if not set locally, 12 hours from the time set by the downloader.
†† The test report is automatically set to repeat: CFV15P = every four weeks; CFV15PCN = every week
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
• Disarms the system when the zone is activated.
• User code for button must be assigned.
• Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
• A report is sent to the central station.
• Assign to zone wired to a keyswitch.
Assign to zone connected to AAV module.
Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops, except for fire alarms,
which immediately terminate the voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout has not expired)
and reports that were stopped are sent.
• These zone types can be programmed for various custom responses. See data fields *182-*185.
UL: Zone types 90-91 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
Group No.
Start Time/
Days
for "02" events:
04 = forced STAY arm
05 = forced AWAY arm
06 = auto disarm
07 = display "reminder"
Stop Time/
Repeat
Days
(0-4)
Installer Only
10 = display custom words 8-10
11 = periodic test report
– 13 –
Random
(yes/no)
††
[no]