Emergi-Lite HP Series Manual

Browse online or download pdf Manual for Remote Control Emergi-Lite HP Series. Emergi-Lite HP Series 2 pages. Remote heads for hazardous locations

HP Series Remote Heads for Hazardous Locations
Class I Division 2, Class II, Division 2 Groups F & G, Class III
Risk of Electrical Shock.
Disconnect Power before Installation.

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always
be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.
All servicing should be performed by qualified service personnel.
2.
Do not mount near gas or electric heaters.
3.
Equipment should be mounted in locations and at heights where it will
not readily be subjected to tampering by unauthorized personnel.
4.
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
5.
Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
Installation Instructions
1. Remove the cover from the back box (See figure 1).
2. Select the entry point on the back box for the conduit and open one of
the knockouts (top or side).
3. Install the conduit fitting rated for Class 1 Div2 (provided).
4. For daisy-chain (input/output) wiring: open a second knockout and
install the conduit fitting rated for Class 1 Div2 (provided).
Wall or Ceiling mount
Install the unit to the wall or ceiling with 4 screws (not included).  
Column mount (option)
a. The universal mounting bracket is an accessory ordered separately
(See figure 2).
b. The bracket can be installed using steel banding for routing around
the column. Standard banding (not provided) must be maximum
3/4-in in width. The bracket can also be mounted on a Superstrut®
metal framing (1 5/8-in channel series) using 1/4-in bolts (not
provided). Holes are placed at 9-in apart horizontally.
c. Install the bracket, observing the indicator: TOP.
d. Screw the unit onto the bracket with the 4 screws, washers and
nuts included in the bracket kit.
5. Route the wires from the wire conduit(s) through the conduit fitting(s)
and into the back box.
Emergi-Lite®
Tel: (888) 552-6467
®
WARNING:
HP Series Remote Heads for Hazardous Locations
Lamps
Figure 1
Figure 2
WARNING:
LED Lamp wattage
Fax: (800) 316-4515
www.emergi-lite.com
Back box
Cover
THE COLUMN MUST BE
ANCHORED TO THE FLOOR
AND CEILING.
Maximum mounting height
as per UL924 standards
Maximum mounting height
6 - Watts
10 - Watts
15 - Watts
Conduit hub
entries(3)
Hook
.
30 Feet
50 Feet
60 Feet
11/17 750.0024 Rev. A
1/2