CLOCK FUNCTION APPLICATION
It is necessary to request a T2 24V control panel with firmware 02.
By connecting a switch and/or a daily/weekly clock (instead of or in parallel to the
open button N.O. "COM-OPEN"), you can open and keep the automation open for
as long as the switch is pressed or the clock remains active. Command functions
are inoperative with open automation.
Releasing the switch or at the preset time, the automation closes immediately.
CLOSE BUTTON (COM-CLOSE)
Controls the closing movement when the gate is stationary.
REMOTE CONTROL
If DIP6 ON =>
It cyclically performs the commands open-stop-close-stop-open
etc.
If DIP6 OFF =>
Opens the gate when closed. There is no effect if activated
while opening. If activated when gate is open, the gate closes. If
activated while closing, the gate reopens.
PEDESTRIAN OPEN BUTTON (COM-PED.BUTT.)
Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any
command linked to the T2 24V board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
If DIP6 ON =>
It cyclically performs the commands open-stop-close-stop-open
etc.
If DIP6 OFF =>
Opens the gate when closed. There is no effect if activated
while opening. If activated when gate is open, the gate closes. If
activated while closing, the gate reopens.
ELECTRIC LOCK (LOCK)
Set DIP 8 to ON to enable control of the electric lock when opening.
ELECTRIC LOCK PULSE RELEASE IN OPENING
Set DIP 9 to ON to enable the electric lock pulse release when opening (provided
DIP 8 is ON).
If a command to open the gate is given when the gate is closed, the closing
movement is performed for 0.5 seconds and the electric lock is simultaneously
activated (followed by a 0.5 second pause and then the opening of the gate).
ELECTRIC LOCK PULSE ENGAGEMENT
Set DIP 10 to ON to enable the pulse engagement of the electric lock when closing.
Upon closing, motors are activated for 0.5 seconds at full voltage to ensure lock
engagement.
EASY MOTOR RELEASE
Set DIP 11 to ON to enable easy manual release (provided that DIP 10 is ON),
upon closing a reverse motion with a fixed time of 0.2 seconds occurs to facilitate
manual release.
O
PERATION OF SAFETY ACCESSORIES
PHOTOCELL (COM-PHOT)
DIP 4 OFF => if an obstacle is placed in range of the photocells when the gate is
closed, the gate does not open. During operation, photocells work
when opening (by starting the opening movement only after the
obstacle is removed) and closing (by starting the reverse movement
only after the obstacle is removed).
DIP 4 ON =>
if an obstacle is placed in range of the photocells when the gate
is closed and the command to open is given, the gate opens (the
photocells do not work while opening). Photocells work only during
closing (with reverse motion restored after a second, even if they are
still engaged).
CONTROL OF IMMEDIATE CLOSING AFTER MOVEMENT IN FRONT OF
PHOTOCELLS
DIP 16 ON and DIP 4 OFF => if photocells are engaged during opening, the gate
stops and the gate only closes one second after the
photocells are disengaged.
DIP 16 ON and DIP 4 ON => if photocells are engaged during opening, the gate
continues to open. Upon disengagement of the
photocells, the gate stops and reverses closing
motion after a one second pause.
If total opening is reached (end of opening time),
immediate closing is deactivated and automatic
time closing is activated (if TCA trimmer is
DIP 12 OFF =>
N.B.: Please check photocell operation at least every six months.
EDGE (SAFETY STRIP) (COM-EDGE)
If engaged during opening, reverses the motion when closing.
If engaged when closing, reverses the motion when opening.
If it remains engaged again, it performs a further reversal after 2 seconds, then
performs an additional short reversal and then gives the sensor failure or engaged
alarm (N.O. contact).
If the sensor remains engaged (N.O. contact) no movement is allowed.
If not used, jump the terminals COM-EDGE.
MONITORING OF SAFETY SENSORS (A+ TEST A-)
Sensors can be monitored through the A+ TEST input and DIP 12 ON.
The monitoring consists of a functional test of the sensor run after every full gate
opening.
Closing the gate is therefore permitted only if the sensors have passed the functional
test after each opening.
CAUTION: MONITORING OF THE SENSOR INPUT CAN BE ACTIVATED WITH
DIP 12 ON OR DEACTIVATED WITH DIP 12 OFF. IN FACT, THE FUNCTIONAL
TESTING OF SENSORS IS 'POSSIBLE ONLY IF THESE DEVICES HAVE THEIR
OWN POWER SUPPLY.
A MECHANICAL SENSOR CAN NOT BE MONITORED, SO DIP 12 SHOULD BE
SET TO OFF.
SENSOR AUTOTEST ALARM (DIP 12 ON)
If the sensor fails the monitoring test after opening, an alarm is displayed by the
blinker lighting up. Gate closure is not allowed in this condition. Normal operation
can be restored only by repairing the sensor and pressing one of the activated
controls.
STOP BUTTON (COM-STOP)
The STOP button stops the gate during any operation.
If held when the gate is fully open (or partially when using the pedestrian control)
automatic closing is temporarily deactivated (if activated by the TCA trimmer and
LED DL6 on). It is therefore necessary to use a new command to make it close.
The automatic closing function is reactivated on the next cycle (if activated by the
TCA trimmer and LED DL6 on).
POWER SENSOR ALARM
The T2 24V control panel has automatic sensors that make the movement of the
gate reverse in case of impact against objects or persons in accordance with the
current EN standards (always use the right tool to ensure compliance with the values
imposed by the standard), without special adjustments on the control panel, as it
operates using special internal software.
If the power sensor is used in opening or closing (only in high-speed) and then
again, in the opposite direction, the gate stops and then reverses for 1 second.
The alarm status will be displayed by the blinker which will remain active for one
minute, during which time you can restore gate operation by pressing any command
button.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE
FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell
fails or remain engaded for more than 60 seconds, the open, close, k button and
pedestrian commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the
programming led.
With the blinking of the programming led, the opening and closing operation are
allowed only with the command button pressed and held. The radio commands
and that of automatic closing, will be excluded, since their use in this mode, is not
allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio
commands and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety
strips (or photocells) the photocells (or safety strips) still work by interrupting
the operation in progress.
Note 2: the stop command is not to be considered a safety command that can be
bypassed in this mode. Therefore, when pressed or damaged, it will not
allow any movement of the gate.