Technical Data For PSB12-015-P
Input (AC)
Nominal input voltage
Voltage range
Frequency
Nominal current
Inrush current limitation. I2t (+25 °C) typ.
Mains buffering at nominal load (typ.)
Turn-on time
Internal fuse
Leakage current
Output (DC)
Nominal output voltage / Adjustment range
Output Power
Nominal current
Derating above +50 °C [122°F]
Startup with capacitive loads
Max. power dissipation idling / nominal load approx.
Efficiency (at 400 VAC and nominal values)
Residual ripple/ peak switching (20 MHz) (at nominal values)
Parallel operation
General Data
Type of housing
Signals
MTBF
Dimensions (L x W x H)
Weight
Connection method
Wire size / torque
Stripping length
Ambient Operating temperature
Storage temperature
Humidity at +25°C, no condensation
Shock
Vibration (Non-operating)
Pollution degree
Climatic class
Certification and Standards
Electrical equipment of machines
Electronic equipment for use in electrical power installations
Safety entry low voltage
Electrical safety (of information technology equipment)
Industrial control equipment
Protection against electric shock
CE
EMC for ITE
EMC for industrial
Limitation of mains harmonic currents
RoHS
Safety and Protection
Transient surge voltage protection
Current limitation at short-circuits approx.
Surge voltage protection against internal surge voltages
Isolation voltage:
Input/output (type test/routine test)
Input/GND (type test/routine test)
Output/GND (type test/routine test)
Protection degree
Safety class
85-264VAC (DC input range 120-375 VDC)
47-63Hz (0 Hz @ DC input)
0.37A @ 115VAC, 0.22A @ 230VAC
< 30A @ 115VAC, < 65A @ 230VAC
> 22ms @ 115VAC, > 110ms @ 230VAC
T 3.15 AH / 250 V (non-replaceable)
12VDC ± 2 % / 11-14VDC (maximum power < 15W)
2.5 % / °C. (>70°C [158°F] 4 % / °C.)
83.5% min.@ 115VAC & 83% min. @ 230 VAC
With decoupling diode
100 mm x 32 mm x 100 mm [3.94 in x 1.26 in x 3.94 in]
0.32-2.1 mm² (AWG 22-14) / 0.79Nm (7.0lb in)
7 mm [0.28 in] or use suitable lug to crimp
-20°C to +50°C [-4°F to 122°F]
-25°C to +85°C [-13°F to 185°F]
30g half sine, 3 times per direction, 6 directions, per IEC60068-2-27
10 to 150Hz, 5 g, 90 min. each axis per IEC60068-2-6
3K3 according to EN 60721
IEC60204-1 (over voltage category III)
EN62477-1 / IEC62103
PELV (EN 60204), SELV (EN 60950)
UL/C-UL recognized to UL60950-1, CSA C22.2 No.60950-1,
CB scheme to IEC60950-1
UL listed to UL508, CSA to CSA C22.2 No.107.1-01
In conformance with EMC directive 2014/30/EU and low voltage directive 2014/35/EU
EN55032, EN61000-3-2, EN61000-3-3, EN55024
EN55011, EN61000-6-2
3PET
E198298
Isurge = 150 % of Po
Class I with GND connection
100-240VAC
< 2.5 sec.
< 1 mA
15W
1.25A
Max. 5,000 µF
m 3.2W
< 100mV
Plastic (PC), closed
Green LED DC OK
> 300,000 hrs.
0.175 kg [0.39 lb]
Screw connection
<95 % RH
2
DIN 57100-410
N/A
Yes
249074
VARISTOR
typically
max
Yes
4 kVAC / 3 kVAC
1.5 kVAC / 1.5 kVAC
1.5 kVAC / 500 VAC
IPX0