As a Direct NET
The DCM can be used as a network interface for applications that require data to be
Interface
shared between PLCs, or between PLCs and an intelligent device (such as a host
computer). The DCM easily connects to Direct NET. This network allows you to
upload or download virtually any type of system data including Timer/Counter data,
I/O information, and V-memory information.
Using a DCM as part of a PLC Network Master — The DCM can be used in a
DL405 PLC station that is serving as a network master. (A master is the network
station that initiates requests for data from other stations on the network). The DCM
takes communication requests issued from the PLC program and automatically
converts these requests into network commands that read data from or write data to
another network station.
The PLC program is really very simple and only requires a few instructions. You do
not have to be a PLC programming guru to use the network. Appendix A provides an
overview of the instructions used. (If you want even more information, see the
Direct NET Manual).
Using a DCM as part of a PLC Network Slave — The DCM can also be used in a
DL405 PLC station that is serving as a network slave station. In this case, the DCM
"listens" to the network for any messages that contain the DCM's address. The DCM
deciphers the network commands, carries out the request to read or write data, and
sends confirmation and/or information to the master station.
esponse
Communicate with
either a PC or
Direct NET Slaves
equest
Introduction
Direct NET Slaves
Slaves respond to
the master's request
5 5