METAL DUCTWORK INSTALLATION
Power Connection Requirements: This device is designed to operate using
a 24 VAC, 40Va transformer. Transformers supplied with a straight cooling
or HVAC system may be used to power the device but must be verified it's
capable of handling the additional device load before installation. If the system
transformer is not capable of handing the extra load, a separate 24 VAC, 40Va
WARNING
transformer MUST be used. Do not connect the device to any power source
with a voltage less than 22 VAC and a maximum of 32 VAC. Doing so will cause
damage to the device.
1. Locate suitable
area of duct for
installation.
ALTERNATE CUTTING METHOD
a. Using the mounting plate,
mark 4 Cutting Method
holes on duct.
5. Remove backing from
mounting plate adhesive
gasket.
8. Insert unit into opening.
Be sure the air will pass
though the ActivePure
Cell honeycomb matrix.
NOTE: Unit requires continuous power. Do not install where power to the unit will be cycled on and off.
2. Cut away insulation
to expose metal
duct (if needed).
b. Drill 4 holes where marked.
6. Center openings and press
mounting plate onto duct. The
adhesive gasket will hold the
mounting plate in place.
9. Secure the unit to the
mounting plate with (4) thumb
®
nuts.
3. Mark location for 3.5"
opening using the
mounting plate.
7. Secure the mounting plate using
(8) #8 self-tapping screws.
4. Cut hole in duct
using 3.5" hole saw.
c. Cut between holes
using tin snips.
1/4