Autometers Systems IC 995 Installation And Operating Manual - Page 8
Browse online or download pdf Installation And Operating Manual for Measuring Instruments Autometers Systems IC 995. Autometers Systems IC 995 10 pages. Electrical network analyser
:
Network
Move the highlighted feature up or down by pressing the arrows marked
the "Network" line. The cursor will move over the "3p4w" symbol to alter this press
the key with the arrows facing the right
3p4w. Select the value you want then press the key with the arrow facing down
, this moves the cursor to the line below.
:
V. Range
You will notice that the 400 v is now highlighted. To change this press the arrow
key marked with the arrow pointing to the right
100V. select the voltage range you require and then press the key with the arrow
marked down
. You will notice the 5A is now highlighted.
:
I. Range
To change I range press the arrow key marked with the arrow pointing to the right
, the number will change to IA. Select the setting you require and then press the
key with the arrow marked down
now highlighted.
: To change this you will need to operate four keys
VT
The two keys which have the arrows pointing up and down
along for you to enter your number in the correct sequence.
The two keys with arrows pointing left and right
or down.
E.g. The cursor will move down over the first number to your left, to move this across to the
next cursor press the key with the arrow facing down
to the right. To increment the number at any point press the key with the arrow marked to the
right. Continue until you have entered the correct numbers.
0400/0400 select the voltage range you require and then press the key with the
arrow marked down
. You will notice the 0005/0005 is now highlighted.
: To change this you will need to operate four keys
C.T. (current transformer ratio)
The two keys which have the arrows pointing up and down
along for you to enter your number in the correct sequence.
The two keys with arrows pointing left and right
up or down.
14
8
this will switch from 1p2w to 3p3w to
the number will change to
. You will notice the 0400/0400 is
.
move the cursor
increment the number up
the cursor has now moved one space
move the cursor
increment the number
E.g. The cursor will move down over the first number to your left, to move this
to
across to the next cursor press the key with the arrow facing down
has now moved one space to the right. To increment the number at any point
press the key with the arrow marked to the right. Continue until you have entered
the correct numbers: 0200/0005.
You must now press the return key
chosen in the meter. a box will appear with yes/no in it
the arrow facing left
this has now programmed the ct ratio.
IMPORTANT
: You will receive the meter in the factory default mode which is suitable for
3 phase 4 wire network, 230/400 volt, 50 hz 0005/0005 amp.
YOU SHOULD ONLY NEED TO PROGRAM THE CT RATIO AND THE TIME INTO THE METER
E.g: 0200/0005 (the date and time)
: You should now be back at the Config Menu:
Select Menu
Move the highlighted feature up or down by pressing the arrows marked up or
down
to the "RS 485" line.
RS 485
: Press the return key
have two features you can alter.
a. Address (meter's unique Modbus number)
b. Baud Rate
a. Address
Please note the meter is factory-set to match Autometers protocol.
Baude Rate: 9600
Parity Type:
Even
Wire Mode:
2 wire
When using RS 485 Modbus it is vital that you understand what management
system the meters will be connected to. Normally every meter must have a unique
address and must not be duplicated.
However, when connecting to Autometers Intelligent Termination Point then all
meters must have the address set at "001".
To change this you will need to operate four keys
The two keys which have the arrows pointing up and down
along from left to right so you can enter your number in the correct sequence.
this will set all the parameters you have
. Press the key with
YES
NO
the cursor has now moved over the "YES" . Press return
this will take you to the RS 485 screen. Here you
Data Format:
Floating point
Modbus Type:
RTU
F.P. High word first
the cursor
move the cursor
15