Celiera KFR-51GW/Ga User Manual - Page 14
Browse online or download pdf User Manual for Air Conditioner Celiera KFR-51GW/Ga. Celiera KFR-51GW/Ga 14 pages. Split wall-mounted air conditioner
[Installation of electric components]
Points of attention
•
HACK type breaker should be utilized along with proper installation;
•
Make sure of the applicable voltage and cables or wires for the specific model to be used, before doing the
connections;
•
Read the prompts at the terminal board for wiring. Make sure the wiring is done correctly.
•
Pay attention to the poles of the signal terminal and connect the terminals to match the identification numbers.
•
When the wiring connections are wrong, the compressor will not work.
•
The connecting wires are not supplied.
•
The connecting wires specification 14 AWG,VW-1(orTHHW),copper core and 105°C for model 5100W and
model 6600W Their set screw diameter is 4 mm.The power sourc is 240V,60Hz and 1 phase.Minimum circuit ampacity
of the wiring systems is 20A.
Connection of wires for outdoor unit and indoor unit
Outdoor unit
1 [2
3 L3L4[©
:
L1 L2 K;
To power source
Note:
•
The environment conditions must be taken into consideration when the connections of power cable are made (such as
the ambient temperature, direct exposure to heat/direct exposure to sunlight);
•
The specifications for the power cable refer to the minimum values of the metal core wires. Taking into consideration
the voltage losses, the core wire of power cable must be one size larger than the specifications;
•
The grounding wire must be connected to the indoor units and outdoor units;
•
The laying of power cables must be done by qualified electricians and comply with the regulations of the local power
supply authorities and with the standards of the electric appliances;