Autonics TC4H Manual - Page 10
Browse online or download pdf Manual for Temperature Controller Autonics TC4H. Autonics TC4H 14 pages. Touch switch type temperature controller
Also for Autonics TC4H: Manual (14 pages), Manual (2 pages), Instruction Manual (2 pages), Quick Start Manual (9 pages), Quick Start Manual (10 pages)
Loop break alarm(LBA)
It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling control), when
control output MV is 100%(0% for cooling control) and PV is not increased over than LBAdetection band [ LBaB ] during
LBA monitoring time [ LBaT ], or when control output MV is 0%(100% for cooling control) and PV is not decreased below
than LBA detection band [ LBaB ] during LBA monitoring time [ LBaT ], alarm output turns ON.
LBA
Temperature
monitoring time
SV
PV
Control
LBA detection
band
output
MV
100%
0%
Loop break
alarm(LBA)
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB ] during LBA monitoring
Start control to ①
time [ LBaT ]
① to ②
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB ] during LBA monitoring
② to ③
time [ LBa ] loop break alarm (LBA) turns ON after LBA monitoring time.
③ to ④
Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
④ to ⑥
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 100% and PV is not increased over than LBA detection band [ LBaT ] during LBA monitoring
⑥ to ⑦
time [ LBaT ], loop break alarm (LBA) turns ON after LBA monitoring time.
When control output MV is 100% and PV is increased over than LBA detection band [ LBaB ] during LBA monitoring
⑦ to ⑧
time [ LBaT ] loop break alarm (LBA) turns OFF after LBA monitoring time.
⑧ to ⑨
The status of changing control output MV (LBA monitoring time is reset.)
※ When executing auto-tuning, LBA detection band[ LBaB ] and LBA monitoring time are automatically set based on auto
tuning value. When alarm operation mode [ AL-1 , AL-2 ] is set as loop break alarm(LBA)[ LBa
[ LBaB ] and LBA monitoring time [ LBaT ] parameter is displayed.
SSR drive output function(SSRP function) [ SSrM]
● Realizing high accuracy and cost effective temperature control with both current output (4-20mA) and linear output(cycle
control and phase control)
● SSRP output is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive
voltage output.
● Select one of standard ON/OFF control [ STND ], cycle control[ CYCL ] , phase control[ PHAS ] at SSrM parameter of
setting 2 group. For cycle control, connect zero cross turn-on SSR (random turn-on SSR is also available). For phase
control, connect random turn-on SSR.
Temperature controller
Power
100-240VAC
50/60Hz
※ When selecting phase or cycle control mode, the power supply for load and temperature controller must be the same.
※ In case of selecting PID control type and phase [ PHAS ] / cycle [ CYCL ] control output modes, control cycle [ T ] is not
allowed to set.
※ For AC/DC power model (TC4 - 2R), this parameter is not displayed and it is available only standard control by relay
or SSR.
LBA
LBA
monitoring time
monitoring time
LBA detection
band
LBA
invalid
①
②
③ ④
(TC4 Series)
SSR voltage output
(12VDC)
Economical PID Control
LBA
monitoring time
monitoring time
LBA detection
band
LBA detection
band
LBA
invalid
⑤
⑥
⑦
SSR Module
INPUT
LOAD
LBA
LBA
invalid
Time
⑧
⑨
], LBA detection band
Load
(A)
Photo
electric
sensor
(B)
Fiber
optic
sensor
(C)
Door/Area
sensor
(D)
Proximity
sensor
(E)
Pressure
sensor
(F)
Rotary
encoder
(G)
Connector/
Socket
(H)
Temp.
controller
(I)
SSR/
Power
controller
(J)
Counter
(K)
Timer
(L)
Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
(O)
Sensor
controller
(P)
Switching
mode power
supply
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
(U)
Other
H-63