Autonics TM Series Product Manual - Page 2
Browse online or download pdf Product Manual for Temperature Controller Autonics TM Series. Autonics TM Series 4 pages. Modular 4-channe pid temperature controllers with screwless connector
Also for Autonics TM Series: Manual (9 pages)
• 24 VDCᜡ model power supply should be insulated and limited voltage/current or Class 2,
SELV power supply device.
• Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of
line to reduce the effect of external noise.
• Make a required space around the unit for radiation of heat.
For accurate temperature measurement, warm up the unit over 20 min after turning on
the power.
• Mounting multiple devices in any way other than the specified mounting method may
cause heat to build up inside, which will shorten their service life. If there is a possibility
of the ambient temperature rising to a temperature above the specified temperature
range, take steps, such as installing fans, to cool the device. Be sure that the cooling
method in not cooling just the terminal block. If only the terminal block is cooled,
measurement errors may occur.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• Install DIN rail vertically from the ground.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T
M
❶
-
❷
❶ channel
❸ Control output
2: 2 channels
R: Relay
4: 4 channels
S: SSR drive
C: Selectable current or SSR drive output
❷ Alarm output
2: Alarm output 1/2
❹ Structure
(2 channels)
B: Basic module
4: Alarm output 1/2/3/4
E: Expansion module
(2 channels)
• Since the expansion module is not supplied with power/
N: None (4 channels)
comm. terminal. Use it with the basic module.
Product Components
• Product
• Instruction manual
• Side connector: 1
• Power/Comm. connector: 1 (only for basic module)
Sold Separately
• Communication converter: SCM-Series
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety
considerations in the manuals.
Download the manuals from the Autonics website.
Software
Download the installation file and the manuals from the Autonics website.
■ DAQMaster
DAQMaster is comprehensive device management program. It is available for
parameter setting, monitoring.
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
• Below is based on basic module.
30
30
2
❸
❹
• Current transformer (CT)
103.5
103.5
86.3
86.3
Specifications
Series
TM2
No. of channels
2 channels
Power supply
24 VDCᜡ ±10%
Allowable voltage
90 to 110% of rated voltage
range
Power consumption
≤ 5 W (for Max. load)
Sampling period
50 ms (2 channels synchronous sampling)
Input specification
Refer to 'Input Type and Using Range'.
• 0.0-50.0 A (primary current measurement
range)
CT input
• CT ratio: 1/1,000
• Measurement accuracy: ±5% F.S. ±1 digit
Option
• Contact
input
ON: ≤ 1 kΩ, OFF: ≥ 100 kΩ
• Non contact
Digital input
residual voltage: ≤ 1.5 VDCᜡ
leakage current: ≤ 0.1 mA
• Outflow current: ≈ 0.5 mA per input
Relay
250 VACᜠ 3 A 1a, 30 VDCᜡ 3 A 1a
Control
SSR
12 VDCᜡ ±3 V, ≤ 30 mA
output
Current
DC 4 - 20 mA or DC 0 - 20 mA (Load resistance: ≤ 500 Ω)
Alarm output
250 VACᜠ 3 A 1a
RS485 Comm.
Modbus RTU
Display type
None- parameter setting and monitoring is available at external devices
Heating,
Cooling
Control
ON/OFF, P, PI, PD, PID Control
type
Heating &
Cooling
Hysteresis
1 to 100 (0.1 to 100) ℃/℉
Proportional band (P) 0.1 to 999.9 ℃/℉
Integral time (I)
0 to 9,999 sec
Derivative time (D)
0 to 9,999 sec
Control cycle (T)
0.1 to 120.0 sec
Manual reset
0.0 to 100.0 %
Mechanical
≥ 10,000,000 operations
Relay life
cycle
Electrical
≥ 100,000 operations (250 VACᜠ 3 A load resistance)
Dielectric strength
Between input terminal and power terminal: 2,000 VACᜠ 50/60 Hz for 1 min
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X, Y, Z direction
Vibration
for 2 hours
Insulation resistance
100 MΩ (500 VDCᜡ megger)
Noise immunity
±0.5 kV square shaped noise (pulse width 1 ㎲) by noise simulator
Ambient temperature -10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Channel insulation
Dielectric strength 1,000 VACᜠ
Double insulation or reinforced insulation (mark: ▱, dielectric strength
Insulation type
between the measuring input part and the power part: 1 kV)
Approval
ᜢ ᜧ ᜣ ᜫ
Unit weight
• Basic module: ≈ 152 g (≈ 217 g)
(packaged)
• Expansion module: ≈ 143 g (≈ 208 g)
Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Decimal
Display
Input type
point
method
1
K (CA) .H
K (CA)
0.1
K (CA) .L
1
J (IC) .H
J (IC)
0.1
J (IC) .L
1
E (CR) .H
E (CR)
0.1
E (CR) .L
1
T (CC) .H
T (CC)
0.1
T (CC) .L
B (PR)
1
B (PR)
Thermo
R (PR)
1
R (PR)
-couple
S (PR)
1
S (PR)
N (NN)
1
N (NN)
C (TT)
1
C (TT)
01)
G (TT)
1
G (TT)
02)
1
L (IC) .H
L (IC)
0.1
L (IC) .L
1
U (CC) .H
U (CC)
0.1
U (CC) .L
Platinel II
1
PLII
JPt100 Ω
1
JPt100.H
JPt100 Ω
0.1
JPt100.L
RTD
DPt100 Ω
1
DPt100.H
DPt100 Ω
0.1
DPt100.L
01) C (TT): Same as existing W5 (TT) type sensor
02) G (TT): Same as existing W (TT) type sensor
■ Measurement accuracy
Using
Input type
Measurement accuracy
temperature
(PV ±0.5% or ±1 ℃ higher one) ±1-digit
At room
• Thermocouple K, J, T, N, E below -100 ℃ and L, U, PLII: ±2 ℃
temperature
±1-digit
(23 ±5 ℃)
• Thermocouple C, G and R, S below 200 ℃: ±3 ℃ ±1-digit
Thermo
• Thermocouple B below 400℃: there is no accuracy standards
-couple
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
RTD
Out of room
• RTD Cu50 Ω, DPt50 Ω: (PV ±0.5% or ±3 ℃ higher one) ±1-digit
temperature
• Thermocouple R, S, B, C, G, L, U: (PV ±0.5% or ±5 ℃ higher one)
range
±1-digit
• Thermocouple below -100 ℃: ±5 ℃
TM4
4 channels
100 ms (4 channels synchronous
sampling)
-
-
22 VDCᜡ ±3 V, ≤ 30 mA
-
• Basic module: ≈ 174 g (≈ 239 g)
• Expansion module: ≈ 166 g (≈
231 g)
Using range (℃)
Using range (℉)
-200 to
1,350
-328 to
2,462
-200.0 to
1,350.0
-328.0 to
2462.0
-200 to
800
-328 to
1,472
-200.0 to
800.0
-328.0 to
1472.0
-200 to
800
-328 to
1,472
-200.0 to
800.0
-328.0 to
1,472.0
-200 to
400
-328 to
752
-200.0 to
400.0
-328.0 to
752.0
0 to
1,800
32 to
3,272
0 to
1,750
32 to
3,182
0 to
1,750
32 to
3,182
-200 to
1,300
-328 to
2,372
0 to
2,300
32 to
4,172
0 to
2,300
32 to
4,172
-200 to
900
-328 to
1,652
-200.0 to
900.0
-328.0 to
1,652.0
-200 to
400
-328 to
752
-200.0 to
400.0
-328.0 to
752.0
0 to
1,400
32 to
2,552
-200 to
650
-328 to
1,202
-200.0 to
650.0
-328.0 to
1,202.0
-200 to
650
-328 to
1,202
-200.0 to
650.0
-328.0 to
1,202.0