Cleaning
The normally high degree of turbulence in the Cross gives a
self-cleaning effect in the liquid channels, which
and the build-up of contamination, which can seriously reduce
heat transfer capacity and increase pressure drop.
Cleaning liquid side
In some applications, the fouling tendency can be very high, for
example with extremely hard water at high temperatures. In
such cases, the Cross can always be cleaned by:
- Circulating a cleaning liquid (CIP – Cleaning In Place).
- A solution of 5% phosphoric acid or 5% oxalic acid in water is
recommended to chemically clean the channels.
- The flow rate of the cleaning liquid should be greater than the
design liquid flow, and the flow should be in the opposite
direction through the heat exchanger relative to the flow in
normal operation.
ATTENTION: After cleaning, it is very important to flush the
-
heat exchanger thoroughly with clean water before start-up.
Cleaning gas side
Heavy condensation can have a self-cleaning effect, washing the
Cross and reducing dirt build-up on the gas side. The Cross 30
has open gas channels at both ends that can be checked
visually. For dry dirt such as carbon, ashes or dust, most of the
dirt sticks to the inlet surface. Cleaning with compressed air or
high-pressure water up to 200 bar is normally effective.
Exhausts from diesel, vegetable oils or biogas combustion may
require regular cleaning.
For greasy dirt such as oil, a suitable cleaning liquid is
recommended. When using cleaning liquid it is important to
flush the Cross thoroughly with clean water before start-up.
Storage
The Cross must always be stored in a dry and protective
environment. The temperature should not be below 1 °C and
not over 50 °C for long-term storage (more than 4 weeks).
During long operational stand-by periods, the system should be
inspected for contamination on the liquid and gas sides. If
necessary, clean the Cross according to the cleaning
instructions. Liquid sides containing water should be drained.
Warranty
Airec offers
a 12-month warranty from the date of installation,
but in no case longer than 18 months from the date of delivery.
The warranty covers only manufacturing and material defects
(poor workmanship and/or faulty material).
The warranty does not cover damage caused by mechanical
(including fatigue damage due to vibrations/pulsations) and/or
thermal stress.
The warranty does not cover damage caused by corrosion.
The warranty does not cover damages caused by dirt build up
and/or fouling.
For further information please see
www.airec.com/support/download.
reduces fouling
Example of CIP set-up
Disclaimer
The
performance of the
Cross
is based on installation,
maintenance and operating conditions being in conformance
with this manual. Airec cannot assume any liability for Cross
heat exchangers that do not meet these criteria.
For further information, please consult Airec's technical information
or your local Airec representative.