Autonics ARD-AI04 Manual - Page 3
Browse online or download pdf Manual for I/O Systems Autonics ARD-AI04. Autonics ARD-AI04 10 pages. Devicenet remote i/o analog, terminal block type
Also for Autonics ARD-AI04: Product Manual (4 pages)
ARD-A Series
Unit Descriptions
1. DeviceNet connector
No.
Color
For
5
Red
24VDC (+)
4
White
CAN_H
3
None
SHIELD
2
Blue
CAN_L
1
Black
24VDC (-)
2. Rotary switch for node address
X10 switch represents the 10's multiplier and X10 switch represents the 1's multiplier.
3. Status
LED:
It is LED for displaying Unit status (MS) and Network status (NS).
4.
Rail Lock:
It is used for mounting DIN rail or with bolt.
5. DIP switch: It is used for set I/O range. (factory default: all switches are OFF)
(●: ON, -: OFF)
ARD-AI04 (Input model)
CH0, CH1
I/O range
SW1
SW2
-
-
0-5VDC
-
1-5VDC
-
0-10VDC
-5-5VDC
-
-
-10-10VDC
-
DC4-20mA
-
DC0-20mA
※ 1: By turning ON SW8, I/O range is set by DIP switches (SW1 to SW6). By turning OFF SW8, I/O range is set by communication.
When setting I/O range by DIP switches, CH0 and CH1 (CH2 and CH3) cannot be set individually.
When setting it by communication, each channel is set individually.
6. I/O Terminal block: It is terminal block for connecting external device I/O.
X-26
2
1
Organization
V+
CAN_H
SHIELD
CAN_L
V-
:
Two rotary switches are used for setting node address.
CH2, CH3
SW3
SW4
SW5
SW6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3
4
5
6
ARD-AO04 (output model)
CH0, CH1
SW1
SW2
SW3
SW4
-
-
-
-
-
-
-
Not supported
-
-
-
-
Not supported
ON
1
2
CH2, CH3
SW5
SW6 SW7
Not
supported
(Off Setting)
-
-
-
-
3
4
5
6
7
8
※1
SW8
ON
Using DIP
switch
OFF
Not using DIP
switch