Also for Emerson E2: Quick Reference Manual (2 pages), Quick Setup Manual (2 pages), Quick Start Manual (8 pages), Instruction Manual (12 pages), Quick Start Manual (14 pages), Quick Start Manual (9 pages), Quick Start Manual (14 pages), Quick Start Manual (9 pages), Installation And Operation Manual (20 pages), Technical Bulletin (8 pages)

Emerson E2 User Manual
pressure control with E2 controllers can often provide savings of 4% or more during
periods of cooler weather, and substantial savings in general any time of the day, week,
month or year when either the fixture heat load or compressor system capacity vary for
any reason. These savings are as compared to a carefully setup and properly working
traditional EPR control-based refrigeration system, the exception rather than the rule in
the supermarket industry. Savings can be much greater when compared to real world
EPR-based systems and conditions.
E2 fixture temperature control with ESRs is very precise (within 1F), allowing the
refrigeration system to support the highest levels of food quality possible. Figure 3
shows data from an actual supermarket that demonstrates the temperature control that
can be achieved with ESRs.
Figure 3. Temperature Control with Evaporator Stepper Regulator.
The use of ESRs has a number of other benefits. With traditional mechanical
EPR valves, a service technician must be physically present at the compressor system
to make adjustments, and has to go through a laborious process that requires the
technician to connect two sets of service pressure gauges, and then adjust the EPR
valve setting by trial and error to obtain the desired evaporator and fixture temperatures.
With E2 and ESRs, anyone can change the temperature setpoint without even being
present in the store, by connecting remotely to the E2 via network or dialup connection
and simply changing setpoints in the E2 controller. A meat case that has held red meat
requiring a 32 degF fixture temperature that is then reset with smoked pork products
requiring 36 degF, can have its operating temperature adjusted easily and remotely
without the expense of a service technician visit. Returning to energy efficiency benefits,
it is important to note that the pressure drop across an ESR when it is fully open is less
than 0.5 psig, resulting in additional energy savings compared to EPRs whenever the