Galletti AREO S 12 Technical Manual - Page 9

Browse online or download pdf Technical Manual for Air Conditioner Galletti AREO S 12. Galletti AREO S 12 12 pages. Aero s series fan heater for steam operation

Galletti AREO S 12 Technical Manual
AREO S
10

ELECTRICAL DATA

Features of the standard motor:
- tropicalised
- equipped internally with a thermal cutout
- IP 55 protection degree
- class F winding
- closed type: asynchronous three-phase 2-speed motors (400/400 V star-
delta connection).
400/400 V - Y∆ motors are equipped internally with a thermal cutout and
speeds are selected by means of a normal star-delta switch (accessory
CST).
The terminals of the cutouts are connected to the terminal block so that they
can be used as protection in series with the coil of a contactor.
If the internal cutout is not used to protect the motor, it will be necessary to
provide a motor overload cutout set at a current that is 10-15% higher than
the current indicated on the unit rating plate.
Model
AREO S 12
AREO S 22
AREO S 32
AREO S 42
AREO S 52
AREO S 62
11

WIRING DIAGRAMS

Delta connection to terminal block of 400/400 V - Y∆ motors, high speed
11
W2
U2
U1
V1
R
Star connection to terminal block of 400/400 V - Y∆ motors, low speed
11
W2
U1
R
Number
of poles
Revolution
4/6
1400 / 900
4/6
1400 / 900
4/6
1400 / 900
4/6
1400 / 900
4/6
1400 / 900
6/8
900 / 700
KLIXON
12
V2
W1
S
T
KLIXON
12
U2
V2
V1
W1
S
T
All copying, even partial, of this manual is strictly forbidden
Make the electrical connections with the power supply disconnected, in
accordance with current safety regulations. All the wiring must be done by
qualified personnel.
Check that the mains electricity supply is compatible with the voltage shown
on the unit rating plate.
Scrupulously follow the wiring diagram provided, according to the type of
installation.
Each unit requires a switch (IL) on the feeder line with a distance of at least
3 mm between the opening contacts, and a suitable safety fuse (F).
Fan
Voltage
rpm
V
400
400
277 / 172
400
394 / 294
400
703 / 471
400
1300 / 860
400
540 / 417
Wiring diagram showing connection of 400/400 V motor, with star-delta
selector (Y∆).
CST
Star-triangle switch
M
Motor
IL
L1
L2
L3
N
14
1
13
6
14
8
10
16
5
15
CST - CSTP
9
Power
Current
Imput
Absorbed
W
A
67 / 46
0,209 / 0,118
0,61 / 0,32
0,85 / 0,58
1,49 / 0,85
2,49 / 1,37
1,18 / 0,69
F
N
1
TA-TA2
2
1
3
5
A1
K
A2
2
4
6
1
13
9
15
2
W1
4
W2
2
U1
U2
6
V1
V2
KLIXON
M
11 12
W2 U2 V2
U1 V1 W1
AP66000271 - 01