Emerson Rosemount 405P Quick Start Manual - Page 8

Browse online or download pdf Quick Start Manual for Industrial Equipment Emerson Rosemount 405P. Emerson Rosemount 405P 18 pages. Compact primary element

Emerson Rosemount 405P Quick Start Manual
Quick Start Guide
Top mounting for steam
Top mounting in steam is an alternative mounting method for steam installations
that can be used if there are space restrictions or other concerns. This installation
method is intended for applications that run with limited interruptions or
shutdowns. Also, for outdoor applications, top mounting can eliminate the need
for heat tracing, if steam is flowing.
Figure 8. Direct mount — 405C, 405P, and 405A
Horizontal top mounting for steam up to 400 °F (204 °C)
A
60°
A. Recommended zone 60°
Note
For the Rosemount 405A Model in wet steam applications, do not mount the flowmeter at
the direct vertical position. Mounting at an angle will avoid measurement inaccuracy due to
water running along the bottom of the pipe.
8
60°
June 2016