FB1100/FB1200 Flow Computer CPU Module Field Replacement Guide
CPU Module (removed)
13.
Use a 3/32-inch flathead screwdriver to separate the internal wire connector plug from the
plug on the bottom of the CPU module.
Internal Wire Connector Plug on CPU Module
14.
If your flow computer includes the 6-channel expansion I/O board (available only on FB1200
units), use a #1 Phillips-head screwdriver to remove the four screws that attach the I/O
expansion board to the CPU module and separate the board from the CPU module. Set the
old CPU module aside and now use those four screws to attach the 6-channel expansion I/O
board to your new (replacement) CPU module. Torque screws to 1 to 2 in-lbs (0.1 to 0.2
N-m).
D301802X012
November 2020