Merlin 1000Si
4
Panel LED status
When the system is connected to the mains supply, the Red LED of the AGS Logo located in
the bottom right corner of the panel will illuminate. When no power is present, this LED will not
light up.
Gas On
When the key switch is turned on, the Merlin 1000Si will check the installation for gas leaks. If gas
proving is successful, the gas valve will open and the 'Gas On' LED will illuminate.
ON = Gas On
OFF = Gas Off
Testing
This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the
integrity of the gas installation upon start up.
ON = proving the gas line, do NOT operate any appliances.
Test Fail
Under normal working conditions this LED is off. When the panel detects a gas leak on start-up,
the LED will illuminate AMBER. Gas valve will remain closed.
OFF = OK
ON = gas proving failed.
Pressure Low
Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of
the gas supply drops below 0.17psi for 10 secs. The gas valve will close.
OFF = OK
ON = gas supply pressure low.
Rev: 05
05-19
User Guide
8