Galvin Engineering Haws 8330-A Product Installation Manualline - Page 5

Browse online or download pdf Product Installation Manualline for Plumbing Product Galvin Engineering Haws 8330-A. Galvin Engineering Haws 8330-A 7 pages. Free standing combi shower, axion msr eye/face wash, hand & foot act
Also for Galvin Engineering Haws 8330-A: Product Installation Manualline (7 pages)

TROUBLESHOOTING

PROBLEM
1. No Flow.
2. Insufficient water flow.
3. Insufficient water flow on eye/face
wash, however, shower is sufficient
4. Eye/face wash streams do not meet
desired eye level.
5. Water does not drain properly.
6. Water leak between joints or fittings.
7. Insufficient water flow from shower,
however, eye/face wash is sufficient.
For more information about GalvinSafe
1.
Check the main shut-off valve.
2.
Verify minimum 210 kPa flowing supply
line pressure.
3. a. Verify minimum 210 kPa flowing supply
b. Probable clogging of flow control due
to inadequate line flushing. Unscrew
eye/face wash head and remove the
four screws to disassemble head.
Clean flow control and reassemble
Head.
c. Remove plug located on L – Strainer
using a 9/16" wrench to access
4. Possible blocked flow control, see above
solution. Possible non-leveled eye/face
wash assembly
5. Check your drain system for debris. Check
the main waste line of your building to see
if it does handle the capacity required for
the entire drainage system
6. Tighten loose connections. If leak persists,
the application of hot water will sometimes
reseat improperly applied joint compound.
After 30 minutes wait and retest. A
persistent leak will necessitate reassembly
and additional sealant.
7. Probable clogging of flow control inside
showerhead. Unscrew showerhead off of
elbow and clean rubber flow control.
®
(Haws) products, see our website.
tth
Version 3.1, 13
REPAIR CHECKLIST
line pressure
clean filter screen.
Aug. 2021, Page 5 of 7