Galvin Engineering 201.10.70.10 Installation Manuallines - Page 4
Browse online or download pdf Installation Manuallines for Control Unit Galvin Engineering 201.10.70.10. Galvin Engineering 201.10.70.10 13 pages. Lead safe thermostatic mixing valve cabinet
Product Installation Guidelines & Scope of Use
201.13.70.10 – CliniMix
5.0 FLOW SIZING GRAPH
The Galvin
Engineering CliniMix
Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown in the graph below. It is important that
the valve is not oversized for its intended application.
© Galvin Engineering Pty Ltd
®
TMV 1500 Lead Safe
™
®
Thermostatic Mixing Valve is suitable for many applications. The Pressure Loss
NOTE: To ensure optimum performance the minimum outlet flow of the
TMV during operation should be at least 4 litres/minute.
It is important that the valve is sized such that the flow rates from the
outlets are not less than those listed AS/NZS 3500.1
The pipe-work between the TMV and the system must be sized in
accordance with AS/NZS 3500.1 to ensure the water velocity in the pipe-
work is within the allowed limit.
If the TMV is to be installed and operated under unequal inlet pressures,
the lower inlet pressure determines the outlet flow rate. However, for
optimum performance and stability it is recommended that the TMV be
installed with balanced dynamic inlet pressures (+/- 10%).
½" Thermostatic Mixing Valve w/ Cold & Hot Bypass in SS
Cabinet
Version 1, 13 November 2023, Page 4 of 13