Galvin Engineering CliniMix TMV 1500 Installation Manuallines - Page 2

Browse online or download pdf Installation Manuallines for Control Unit Galvin Engineering CliniMix TMV 1500. Galvin Engineering CliniMix TMV 1500 13 pages. Lead safe thermostatic mixing valve cabinet

Product Installation Guidelines & Scope of Use
1.0 DESCRIPTION
This manual covers the CliniMix
provide tempered water to the desired outlets. This mixing valve cabinet assembly is supplied with integral
isolating valves, strainers and check valves and is provided with a facility for thermal disinfecting of the cold inlet
side and mixed water outlet.
Avoid using heat for soldering near the mixer inlets to prevent damage to internal components.

2.0 TECHNICAL DATA

MIXED OUTLET TEMPERATURE
Factory Preset Temperature
Adjustable Temperature Range (°C)
INLET TEMPERATURES
Cold Supply (°C)
Hot Supply (°C)
Hot to Mix Temp Differential (°C)
Cold to Mix Temp Differential (°C)
Nominal Flow Rate (LPM)
DYNAMIC INLET PRESSURES
Hot and Cold Inlet Pressures
STATIC INLET PRESSURE
Hot and Cold Inlet Pressures (kPa)
INLET PRESSURE RATIO
Supply Pressure Loss Ratio
Recommended Supply Pressure Variation (Hot:Cold or Cold:Hot)
Minimum Flow Rate to Ensure Stable Operation
NOTE 1: For optimum operation it is recommended that the hot and cold water supply pressure be balanced to within +/- 10%
NOTE 2: Notwithstanding the above, compliance with AS/NZS3500 must be maintained.

3.0 SAFETY

®
The CliniMix
TMV 1500 Lead Safe
stable and dependable operation, provided it is installed, commissioned, operated and maintained as per the
recommendations outlined in this manual. It should be noted, however, that this valve should not be considered
as an alternative to adequate supervision and duty of care during its use and operation.
Note: The mixing valve, inlet controls, pipe work and the surrounding area may become hot when
installed which may cause burn injuries. Precautions should be taken to ensure that these
surfaces cannot cause such injuries.
© Galvin Engineering Pty Ltd
®
TMV 1500 Lead Safe
(°C)
TMV SS Cabinet Assembly is a high-performance valve designed to give
TMV SS Cabinet Assembly. This product is designed to
Version 1, 13 November 2023, Page 2 of 13
43 +/- 2
35 – 50
Min
5
Max
30
Min
55
Max
90
Min
10
Min
5
Min
4
Min
20
Max
600
Max
1600
Max
10:1
±10%
4 L/min