AGS PARKSAFE GAS DETECTOR Installation Operation & Maintenance - Page 4

Browse online or download pdf Installation Operation & Maintenance for Gas Detectors AGS PARKSAFE GAS DETECTOR. AGS PARKSAFE GAS DETECTOR 16 pages.

Installation, Operation & Maintenance

INSTALLATION

Planning

Our detectors should be installed in areas at risk of gas accumulation.
Take in to account the design of the air flow patterns within the parking zone area. Detectors should be
installed in the correct orientation, as recommended by the manufacturer, and ease of access should be
accounted for to allow for any bump tests and other forms of maintenance and identification.

Typical Location and Positioning

Consider the coverage required and function of the area. Emphasis should be placed on airflow patterns
and correct placement, not perceived detecting ranges. The target gas will only be identified when
contact is made with the sensing element itself.
Locations for Parksafe gas detectors will vary based on the intended application and target gas, they
should be located near where hazardous gas could quickly accumulate and areas of identified
consequential risk. The composition of the target gas and its density relative to air are used as the basis
for the recommended height of gas detectors. These heights may vary based on air flow and temperature
conditions in addition to the proposed application and location.
Carbon Monoxide (CO) gas
Nitrogen Dioxide (NO
Avoid conditions of any other environmental factors that could potentially impede the accuracy and
operation of the detectors such as; condensation; vibration; temperature, pressure, the presence of other
gases, electromagnetic interference and draft areas.

Typical Installation Arrangement

The gas detectors are designed around a centralised Parksafe control panel of which the location also
needs to be considered. The panel should be located away from the hazardous area that it is monitoring.
Accessibility is required both for status observation and alarm purposes.
Where connections may exceed 500 yards from one control panel – Contact your supplier!
The use of sound strobes are highly recommended!
Rev: 9 10-20
Breathing Zone - 1700mm (5ft 6") from ground level.
) gas
Low Level - 300mm (1ft) from ground level.
2
Parksafe Gas Detector
4