AGS Merlin GDP2 Installation Operation & Maintenance - Page 10
Browse online or download pdf Installation Operation & Maintenance for Control Panel AGS Merlin GDP2. AGS Merlin GDP2 12 pages. Safe area gas detector controller
Also for AGS Merlin GDP2: User & Installation Manual (7 pages), User Manual (12 pages)
Installation & Operation Manual
End of Operational Life (EOL)
The typical life of a gas detector depends on its application and intended target gas, in addition, the operational life
can be prolonged if the system and equipment is installed and maintained in accordance the instructions stated
within this manual.
•
Natural Gas /Methane: 10 Years approx.
•
Liquid Petroleum Gas: 10 Years approx.
•
Hydrogen: 10 Years approx.
•
Carbon Monoxide: 5 Years approx.
At the end of this time, contact your supplier and replace the unit immediately.
Specification
General
Product:
Use:
Indicators
Mounting
Electrical
Max. Power Consumption
Power Voltage Input Range
Gas Valve Output Range
I/Os
BMS
Relay(s)
Terminal Wire ratings
Fuse
Construction
Dimensions (H x W x D)
Unit Weight (Approx.)
Housing Material
Environmental
Ingress Protection
Storage Conditions
Operating Conditions
Compliance
CE
Rev: 8 03-21
GDP2 Gas Detector Controller
Indoor, Safe Areas (not to be used in potentially explosive atmospheres)
LED
Wall Mounting
20W Max (Full Load)
100-120vac
100-120vac
24vdc Outputs (Detector / Strobe or Sounder)
3x Open/Close Switches (EM Stop / Heat Sensor / Fire Panel)
Volt Free (Normally Closed / Common / Normally Open) 3A Max
2x 120vac 10A (Latching Switch)
Copper 18AWG (0.75mm2) Min. x29 screw terminals.
3.15A
140 x 190 x 62mm (5.51 x 7.48 x 2.44")
0.7kg / 24.7oz
Polylac - PA765
IP65 (Pre-installation)
Dry. Cool. Flat
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% rf
EN 61326-1 / BS EN IEC 61010-1
Merlin GDP2
10