3.1 Operation with DALI
The dimmer XLED CV DALI works according to the
DALI standard. Device type 6 (LED module).
The device search assigns a short address to each
of the 4 device channels (or channel groups if chan-
nels are linked). Please see for further information
the operating instructions for your DALI controller
or gateway.
3.2 Operation with 230V PushButton
Alternatively, the DALI input can also be used as a
PushButton input.
A voltage of 230V AC is connected to
the DALI contacts. (**) Button 230V
against N at the DALI input (not SELV)!
WARNING - Due to the fact that 230V are
applied, no further DALI operating device
may be connected in the same circuit when
using the DALI input as a PushButton!
3.3 Operation with DeviceButton
SELECT-Button
Functions SELECT-Button
Channel selection (starting with channel 1) for
manual dimming via the SETUP-Button.
If channels are linked accordingly selection.
Confirmation by flashing the STATUS LED.
Physical selection via DALI
Procedure Physical Selection:
1.
Select DALI command "PHYSICAL SELECTION"
2.
Press SELECT-Button 1x (select channel 1)
3.
When pressed again, the next channel (or
linked channel group) is selected, after channel
4 it starts again with channel 1
4.
Confirmation by STATUS LED flashing
Reset factory settings
There is a reset of all parameters in the delivery state.
A successful reset is signaled by the status LED.
! Reset within 30 minutes after POWER_ON.
As usual in DALI, each of the four DALI short-
addresses of a device can be assigned to any
groups and scenes.
Power On Level = MASK (the last stored bright-
ness value is taken over after approx. 90 sec. As
last memory level) and will be set at the next
power up.
Multiple buttons can be used in parallel, also
several PushButton compatible devices can be
operated in parallel.
Functions with external PushButton
Switch On- / Off
Dimming Up and Down (Start at Min Level)
Switching to Max Level
Synchronization of the connected devices
SETUP-Button
keystroke
Functions SELECT-Button
Switch On- / Off
1...4 x short press
Selection channel 1-4 or
Dimming Up and Down (Start at Min Level)
channel group
Switching to Max Level
1...4 x short press
Selection channel 1-4 or
channel group
press 10 sec.
www.maintronic.de
keystroke
short press
long press
2x short press
press 10 sec.
keystroke
short press
long press
2x short press
4