11.2.
ROUTINE MAINTENANCE
Every 6 months: Check the condition of the coil and condensate drain:
If necessary:
– remove any dirt from the coil surface
– remove dust using an air compressor
– wash with water and brush gently
– dry by using compressed air
– keep the condensate drain free from any obstructions that may prevent normal water flow
Bleed air from the system.
1. start the circulation pump and open the supply valve for a few minutes.
2. stop the circulation pump.
3. loosen the vent screw on the inlet collector and bleed the air.
4. repeat steps 1 to 3 until there is no more air escaping the system
11.3.
ELECTRICAL CIRCUIT
The following steps are recommended to perform maintenance on the electrical circuit:
– check the unit's power consumption using a clip-on meter and compare the reading with the values
shown in the documentation;
– inspect the electrical contacts for corrosion and loose wires.