PARAMETER SETTINGS

–  switch the thermostat off with the "
–  To go to the menu, press the "M" and "+" buttons simultaneously for 10 sec. until " " appears. Adjust the settings with the "+" or "-" buttons.
–  scroll through the menu with the "M" button.
MENU
DESCRIPTION
01
Temp. Offset
03
Maximum temperature
04
Minimum temperature
05
Display mode
06
Dead Band           
07
Frost protection
09
Sensor selection
10
Reboot memory
11
2-pipes/4-pipes select
12
(0-10V) select dead band or not
13
Mode
14
Fanspeed
15
Maximum fan speed
16
Medium fan speed
17
Low fan speed
18
Factory reset
10D7 Software version       
" button
ADJUSTABLE
-8°C ... +8°C (+0,5°C)
+10 °C ... +40°C (+0,5°C)
+10 °C ... +40°C (+0,5°C)
Room / Set / Room set
0°C ... +3°C (+0,5°C)
+10 °C ... +20°C (+0,5°C)
NO / NC
'0': do not save / '1': save
'2': 2-pipe connection / '4': 4-pipe connection
'0': With dead band / '1': Without dead band
Heating / Cooling / Heating + Cooling / Auto select (enkel 4-pijps)
80% - 90% - 100% / Auto mode
80% ... 100%
45% ... 75%
20% ... 40%
'0': not back to factory settings / '1': Factory reset
After selecting "1", press the "
was successful.
10D7 - Version 27
" button to go to the startup window. Recovery