Centrica PAN-42 Operation And Maintenance Manual - Page 6
Browse online or download pdf Operation And Maintenance Manual for Accessories Centrica PAN-42. Centrica PAN-42 11 pages.
PAN-14 Sensor installation guide
Safety precautions
The sensor must be installed only on an insulated conductor.
CTs output/secondary current
The sensor and CT should be installed and removed only by a qualified
electrician.
Installation must not be performed on a live wire for reasons of safety and
random shock hazard. Power supply to the panel must be shut off before and
during installation.
The sensor and CT must not be installed lying or touching bus bars or any other
non-insulated, exposed conductors.
Installation is possible both on external entry/exit conductors before the
terminal strip, as well as both ends of the circuit breaker. The least cramped,
most accessible location should be chosen for installation. The sensor should be
installed such that the arrow points in the direction of the load.
Caution Protection provided by the equipment can be impaired if used in a
manner not specified by the manufacturer.
Mapping the site
See
Panoramic Power deployment
Installing the sensor
PAN-14 and the associated current transformer should be installed in a location
not accessible to an average user. The voltage and current measurement circuit
insulation should be adequate for 300V, CAT III, double/reinforced insulation
from mains.
This procedure must be carried out by a certified electrician.
1. Connect the PAN-14 sensor to the CT by connecting the two CT's
outputs to the PAN-14 sensor using 1.0-4.0mm
follows:
a. Connect the PAN-14 sensor's terminal marked as '1' to the CT's
terminal marked as 'S1' or 'X1'
b. Connect the PAN-14 sensor's terminal marked as '2' to the CT's
terminal marked as 'S2' or 'X2'
Caution A loose or improper CT connection can become a fire hazard! When
connecting the unit to the CT make sure that both CT wires are properly
inserted and that the connector's screws are well tightened, at a torque of
0.45 Nm (4 in-lb). Do not use solder-tipped CT wires.
Revision 3.0 September 2019
© 2019 Centrica plc. Registered office: Millstream, Maidenhead Road, Windsor, Berkshire. SL4 5GD.
Registered in England & Wales No 3033654
must not
exceed 5A.
guide.
2
(12-17 AWG) wires, as