aguilera AE/SA-MC5 Technical Manual - Page 2

Browse online or download pdf Technical Manual for Control Unit aguilera AE/SA-MC5. aguilera AE/SA-MC5 2 pages. Algorithmic master modules

WIRING SCHEMATIC
Assembly
For the installation of the modules, open the module cover by pressing on its central part. Secure the module with 4
screws using the fastening holes foreseen for this purpose.
Wiring
Disconnect the supply voltage of the detection loop before installing the module.
Connect the positive input of the detection loop to the + B terminal.
Connect the negative input of the detection loop to the - B terminal.
Module AE/SA-M
Module AE/SA-MC5
Ae-man-823-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
Module AE/SA-MDL
Once the connections have been made, close the module, taking care that the status LED remains visible.
VERIFICATION OF OPERATION
The modules must be tested after installation and undergo periodic maintenance.
Before carrying out the operating tests, notify to the competent authority that maintenance tasks are being carried out
in the fire detection system. Make sure that the automatic extinguishing tripping functions are disabled. Make sure that
the automatic extinguishing functions are disabled.
TECHNICAL MANUAL
Ae-man-823-0.0 v1.1
When removing the module connection plug, the area should be put in the fault state. If this is not done, check it
is correctly programmed in the Algorithmic Panel.
Check that the module is working, by observing that it emits red colored flashes every 10 s, provided this
function has not been inhibited individually. If the flashing is not inhibited and the module does not emit them,
this means it has failed or the wiring is faulty.
Activate the module output from the Algorithmic Panel. Check their activation in the module. The frequency at
which the luminous indicator flashes will also increase.
Restore the output to the idle state. To reset the system, press the RESET key on the Panel.
Activate the loop detectors and check that the zone passes to alarm state in the Algorithmic Panel.
To reset the system, press the RESET key on the Panel.
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
TECHNICAL MANUAL