Centrometal EKO-CKB 20 Use And Maintenance - Page 17
Browse online or download pdf Use And Maintenance for Boiler Centrometal EKO-CKB 20. Centrometal EKO-CKB 20 20 pages. Cm pelet-set (14-35 kw)

Pellet feeding tube
E3 – excessive
temperature at burner
temperature on
above
feeding tube
80°C
E4 – boiler
Error in boiler
temperature sensor
temperature sensor
Error in temperature
E5 – sanitary water
sensors in sanitary
temperature sensor
water tank.
Photocell does not
E6 – flame
detect flame in the
disappeared
burner combustion
chamber.
E7 – error in
Memory failure
memory
Sensor of revolution
E8 – fan
number does not "see"
malfunction
fan rotation
E9 – backfilling
Backfilling supply tube
supply tube with
with pellets
pellets
Due to power supply
interruption in safety
time
E230 –error E2 or
(12 min.) flame did not
E6 due to power
occur or photocell
supply
does not detect flame
interruption
in the burner
programme before
reaching the set
programme
Technical instructions Cm Pelet-set
burner so pellets can drop freely into the burner;
the burner grate is located correctly in the burner
(that it does not rest ON electric heater);
pellets are not too moist;
pellets are of appropriate size (for these burner
setting they should have diameter of 6 mm);
hot air blows from the burner (i.e. whether electric
heater has not blown);
the photocell sensor is clean.
Possible fan stoppage.
Possible filling up of the burner combustion chamber
and feeding tube due to wrong set of combustion air
wrong set parameters of charge,
inadequate size or quality of pellets, incorrectly set
air in combustion chamber.
Inappropriate pellet size and quality.
Possible hole in flexible tube or disconnection of
flexible tube from feeding tube.
possible delays fan.
Check sensor position.
Check damages of sensor and cables.
Check contacts on connectors.
Check sensor position.
Check damages of sensor and cables.
Check contacts on connectors.
Due to lack of pellets, feeding of too moist pellets, or
due to dirty photocell.
Resetting of control unit to factory setting is required.
Due to failure of rpm sensor, due to failure of fan
bearings (check whether it can rotate freely), due to
entrance of foreign object into the fan rotor, due to
activation of fan overheating protection (after cooling
down by 30°C fan can be restarted).
Check the burner grate fill, burner combustion
chamber, combustion chamber of the boiler, flue gas
tube and chimney, is the burner grate is properly
placed in the burner (that is not set to the electric
heater), whether the pellets are moist, not properly
size or quality of pellets (for these burner settings is
properly diameter of 6 mm), possible holes in a
flexible tube, incorrectly configured parameters of
charge, incorrectly adjusted air combustion.
Check filling up level of the burner grate, burner
combustion chamber and check possible methods to
eliminate errors E2 and E6.
,
17