Seperator alarm OSA 3 • Manual
Press the reset button, the following should
then be displayed.
Level alarm act.
When this has been displayed, lower the
sensor into the separator again. The sensor
should then return to "Normal operation
screen" after up to 60 seconds.
• Testing of damming sensor R6-S
Lower the damming sensor into water,
e.g. water, and wait. The following screen
should be displayed within approx. 60
sec.
Press the reset button, the following should
then be displayed.
High level alarm act.
press [Reset] to
acknowledge sound
High level alarm act.
When this has been displayed, remove the
sensor from the water and wait for up to
2 minutes. The unit should then return to
"Normal operation screen".
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • [email protected] • www.afriso.se
• Testing of sludge sensor ES8
Lift the sludge sensor up into the air and
wait.
The following screen should be displayed
within approx. 60 sec.
Sludge alarm act.
press [Reset] to
acknowledge sound
Press the reset button, the following should
then be displayed.
Sludge alarm act.
When this has been displayed, suspend the
sensor in the water again and wait for up
to 2 minutes. The unit should then return to
"Normal operation screen".
Once all tests have been carried out, the
unit is ready to use.